Aparton SPD-3.1M User Manual Download Page 1

USER’S

MANUAL

SPD-3.1M

SMOKE OPTICAL DETECTOR

1. PURPOSE

1.1 The SPD-3.1M smoke optical point detector is designed to detect smoky fires indoors, and for

transmission of the alarm signal to fire alarm control panels.

1.2 The SPD-3.1M is counted on the continuous 24-hours operating in connection with fire alarm

& fire-intruder control panels in DC or alternating 2-wire fire alarm loops with     the 12/ 24V  rated
supply voltage.

1.3 The detectors have functions:

-

Indication of the standby mode (LED periodical flashing);

-

Indication of the alarm mode (LED steady light).

         The detector complies with EN 54 – 7:2000/ 1:2002/ 2:2006.

2.  TECHNICAL SPECIFICATIONS

2.1 Supply voltage range, V..…………………………..   10-30
2.2 Way of output signal issue  …………………………  non-contact
2.3 Wiring to control panel……………………………..  2-wire
2.4 Standby current consumption, mA………….. ….... 

0,095

2.5 Alarm current consumption, mA………………….. 

6-30

2.6 Internal resistance in alarm mode at 20 mA, Ohm ..  

500

2.7 Reverse current at -30V,  A……………………….. 

5

2.8 Dimensions, mm. …….………..…………  ..…...... 

Ø100   48

2.9 Weight, g ……….………………….…..………..... 

150

2.10 Operating temperature range, °  …...................…. 

from - 10 to + 55

2.11 Average lifespan, years. ………................…….…. 

10

3. Items supplied with the detector

 3.1 The items supplied with the detector are adduced in Table.

Name

Quantity

Note

SPD-3.1M
smoke photoelectric detector

up to 25 pcs.

B103-02 base including

Manual

1 pc.

per a package

Package

1 pc.

per 25 detectors

3.2. The K-4 mounting rings can be supplied by a purchase order for installation of the detectors
on suspended ceilings.