19
June 2012
Gas Controller
AUTOMATIKPRODUKTER
4.6.8
Control Mode Current or Average Value
Definition of the alarm evaluation by current value CV) or average value (AV).
Symbol
Description
Default
Status
Function
MP01.1
Measuring Point
Selection MP No./ bus or analog transmitter
CV
Evaluation
CV
CV = Control by the current gas value
AV = Control by the average gas value
Current/ average value function see also 4.8.6
4.6.9
MP Fault Assigned to Alarm
In this menu you can define, which alarms are activated by a fault at the measuring point.
Symbol
Description
Default
Status
Function
MP01.1
Measuring Point
Selection MP No./ bus or analog transmitter
Alarm - 1 2 3 4 5
Fault - 1 1 0 0 0
Failure MP
1 1 0 0 0
0 = Alarm not ON at MP failure
1 = Alarm ON at MP failure
4.6.10 Alarm Assigned to Alarm Relay
Each of the 5 alarms can be assigned to any physically existing alarm relay
.
Unused alarms are not
assigned to an alarm relay. See also 4.8.16 Relay Multiplication.
Symbol
Description
Default
Status
Function
MP01.1
Measuring Point
Selection MP No./ bus or analog transmitter
01
A1
A2
A3
A4
A5
01
02
03
04
00
01 = Alarm 1 activates alarm relay R 01
02 = Alarm 2 activates alarm relay R 02
03 = Alarm 3 activates alarm relay R 03
04 = Alarm 4 activates alarm relay R 04
00 = Alarm 5 doesn’t activate any alarm relay
4.6.11 MP Signal Assigned to Analog Output
The measuring point signal can be assigned to one of the max. twelve analog outputs. The signal defined in
the control mode (current or average value) is transmitted.
Analog output, see also 4.8.15.
Symbol
Description
Default
Status
Function
MP01
Measuring Point
Selection MP No./ bus or analog transmitter
0
AX
0
0 = MP Signal not assigned to any analog output
1 = MP Signal assigned to analog output 1
X = MP Signal assigned to analog output X