Replace a microinverter
Follow the procedure to replace a failed APsystems
Microinverter.
A. Disconnect the APsystems Microinverter from the PV Module, in the
order shown below:
1. Disconnect the AC by turning off the branch circuit breaker.
2. Disconnect the first AC connector in the branch circuit.
3. Disconnect the PV module DC wire connectors from the
microinverter.
4. Remove the Microinverter from the PV array racking.
5. Cover the module with an opaque cover.
B. Install a replacement Microinverter to the rack. Remember to observe
the flashing LED light as soon as the new Microinverter is plugged
into the DC cables.
C. Connect the AC cable of the replacement Microinverter and the
neighboring Microinverter to complete the branch circuit connections.
D. Close the branch circuit breaker, and verify operation of the replacement
Microinverter.