Page 1: ...AOX Q ELECTRIC ACTUATOR The Instruction Book ...

Page 2: ...afety Instructions 2 Summary 3 Performance Features 4 Primary Technical Parameter 5 Structure 6 General Drawing 7 Wiring Diagram 8 Installation of Electric Actuators 9 Debug Description 10 Running Test 11 Maintenance ...

Page 3: ...and other similar products such as butterfly valve ball valve damper flapper valve cock valve etc It widely applies to petroleum chemical water treatment shipping paper making power plant heating light industry and other industries Drived by 380V 220V 110VAC power or 24V 110VDC power inputs 4 20mA or 0 10VDC control signal moves valve to the right position and achieves to automatic control maximum...

Page 4: ...rotection to avoid the damage of valve and electric actuator when jammed by cutting power automatically 3 8 Self locking Accurate worm and worm gear transfer large torque efficiently high efficiency low noise max 50 dB long life with self locking prevent inversion as stable and reliable transmission parts no need to refuel 3 9 Anti off bolt The bolt attaches to the shell and be not off when remove...

Page 5: ...6 31 Φ35 90 1 85 1 86 0 92 0 92 0 35 0 35 0 34 0 34 13 5 22 AOX Q 050 500 26 31 Φ35 90 3 60 3 62 1 55 1 58 0 59 0 59 0 58 0 58 13 5 23 AOX Q 060 600 26 31 Φ35 120 3 65 3 62 1 60 2 20 0 60 0 59 0 59 0 58 13 5 23 AOX Q 080 800 31 37 Φ45 180 4 10 4 10 2 15 2 20 0 85 0 85 0 79 0 79 16 5 29 AOX Q 120 1200 31 37 Φ45 180 4 20 4 10 2 35 2 30 0 87 0 87 0 81 0 81 16 5 29 AOX Q 150 1500 78 93 Φ45 120 3 65 3 ...

Page 6: ...ing temperature Internal placed thermal protection Open 115 5 Close 97 5 Indicator Continuous position indicator Manual operate Declutching mechanism operate by handwheel Self locking device Self locking by worm and worm gear Mechanical limit 2 external adjustable stopper Space heater 30W 110V 220VAC Conduit entry 2 PF 3 4 Ambient temperature 20 70 Lubrication Grease moly EP type Material Steel Al...

Page 7: ...eries 8 Torque switch SPDT 2 250VAC 10A Except AOX Q 005 008 010 9 Electric current position sensor output 4 20mA DC AOX Q series 10 Self reset when power failure AOX Q series 11 High temperature resistance actuator 10 100 AOX Q series 12 Low temperature resistance actuator 40 70 AOX Q series 13 Low speed actuator AOX Q series 5 Structure Electric actuators is make up of the following parts Housin...

Page 8: ...236 Φ90 Φ70 4 M8 Φ20 140 40 AOX Q 015 351 227 270 Φ125 Φ102 4 M10 Φ70 4 M8 Φ22 140 45 AOX Q 020 351 227 270 Φ125 Φ102 4 M10 Φ70 4 M8 Φ22 140 45 AOX Q 030 367 242 290 Φ150 Φ125 4 M12 Φ102 4 M10 Φ35 140 55 AOX Q 050 367 242 290 Φ150 Φ125 4 M12 Φ102 4 M10 Φ35 140 55 AOX Q 060 367 242 290 Φ150 Φ125 4 M12 Φ102 4 M10 Φ35 140 55 AOX Q 080 410 276 330 Φ180 Φ140 4 M16 Φ140 4 M12 Φ45 140 65 AOX Q 120 410 27...

Page 9: ...18 Φ140 4 M16 Φ45 140 454 696 AOX Q 200 410 276 330 Φ285 Φ165 4 M18 Φ140 4 M16 Φ45 140 454 696 AOX Q 300 410 276 330 Φ285 Φ165 4 M18 Φ140 4 M16 Φ45 140 454 696 AOX Q 400 410 276 330 Φ285 Φ165 4 M18 Φ140 4 M16 Φ45 140 454 696 AOX Q 500 410 276 330 Φ285 Φ165 4 M18 Φ140 4 M16 Φ45 140 454 696 AOX Q 600 410 276 330 Φ285 Φ165 4 M18 Φ140 4 M16 Φ45 140 454 696 ...

Page 10: ... 9 7 Wiring Diagram 7 1 AOX Q 005 010 110 220VAC 50 60Hz 1Ph on off model Picture 3 7 2 AOX Q 015 600 110 220VAC 50 60Hz 1Ph on off model Picture 4 ...

Page 11: ... 10 7 3 AOX Q 005 010 110 220VAC 50 60Hz 1Ph modulating model Picture 5 7 4 AOX Q 015 600 110 220VAC 50 60Hz 1Ph Standard modulating model Picture 6 ...

Page 12: ... 11 7 5 AOX Q 015 600 380V 440V AC 50 60Hz 3Ph External standard on off model Picture 7 7 6 AOX Q 015 600 110 220VAC 50 60Hz 1Ph Intelligent on off model Picture 8 ...

Page 13: ...rmediate temperate bracket when the fluid temperature is over 65 with intermediate temperate bracket High temperature bracket when the fluid temperature is over 180 with high temperature bracket 8 2 Mounting with Valve 8 2 1Turn valve by hand and check the situation then turn to full closed position 8 2 2 The drive shaft is removable and solid before leaving factory picture 9 Note the size of driv...

Page 14: ... by screwdriver meanwhile insert the leadwire to lateral cavity And then remove screwdriver Picture10 Picture 11 9 Debug Description 9 1 Adjustment of Mechanical Limit Loosen the mechanical limit stoppers and locknuts turn handwheel one circle one side move the clutch handle in left until occlude continue to turn the handwheel until the actuator move to the full close position Turn nuts until touc...

Page 15: ...hen actuator in closing movement Note The potentiometer resistance should be not subzero jump phenomenon Turn valve to the full open position by manual until limit switch move measure with a multimeter adjust the resistance between and between 35 Ω 60 Ω If incorrect adjusting by turning the drive gear of potentiometer 9 4 Adjustment of Over torque Protection Device At nominal working pressure adju...

Page 16: ...nsed Position transform precision 0 5 1 5 Dielectric Vol Proof 1500AC min Input to output Power supply to each Shock or impact X Y Z 10g 10 Running Test 10 1 Manual Operation Cut power before manual operation turn the handwheel one circle one side move the clutch handle in left until occlude continue to turn handwheel to decrease the opening observe the opening by window glass 10 2 Electric operat...

Page 17: ... signal If the electric actuator runs to the open direction the wiring is correct If the running direction is opposite change 2 pieces wiring in 3 11 Maintenance Lubrication Because special Mo based grease is long life and well resistance so no need to refuel Regular operation Drive and check the device regularly when valve works infrequently Note Debugging description of modulating model please r...