Anybus X-gateway CANopen

Installation Sheet

online: www.anybus.com

1
3
5

2
4
6

Fieldbus specific

Device Status

CANopen Subnet Status

Fieldbus Specific

LED Ind.

Fieldbus specific

Fieldbus specific
Fieldbus specific

Module Front View

Bottom View

LED Indicators

LED no

Indication

Meaning

1-4

Fieldbus specific, see respective fieldbus installation sheet.

5 (CANopen 

Subnet Status)

1

Off

Power off

Flickering green/red

The LSS services are in progress

Blinking green

Pre-operational state

Single flash, green

Stopped state

Green

Operational state

Blinking red

Configuration error

Single flash, red

Warning limit reached

Double flash, red

Error control event

Triple flash, red

Sync error

Quadruple flash, red

Data communication time-out

Red

Bus off

6 (Device Status) Off

Power off

Single flash, green

Bootup

Green

Running

Single flash, red

Initialization error

Double flash, red

Timeout

Triple flash, red

Hardware failure

Quadruple flash, red

General error

Red

Fatal error

1. This LED shows the status of the CANopen subnet that is controlled by the 

 X-Gateway CANopen.

Accessories Checklist

The following items are required for installation:

• 

CANopen configuration tool (available at www.anybus.com)

• 

CANopen adapter for configuration tool (not included)

• 

CANopen cable (not included)

• 

EDS file, available at www.anybus.com

Installation and Startup Summary

• 

Connect the gateway to the CANopen network.

• 

Select baud rate and an unused node address for the interface. 

(Cover the switches with the enclosed switch covers.)

• 

Install the EDS file in the CANopen configuration tool.

• 

Power up and (if required) configure the module.

Please note that the module will start up as a CANopen slave. The mod-

ule can be reconfigured as a CANopen master during configuration.

CANopen Support

Technical support regarding the CANopen fieldbus system should be 

addressed to CAN in Automation (CiA).

Online: www.can-cia.de

CANopen Connector

Pin no.

Description

2

CAN_L

5

Shield

7

CAN_H

3, 6

CAN_GND

1, 4, 8, 9

(not connected)

USB 

connector

Power:

1. +24 V DC

2. GND

Side View

The three rotary switches 

on the side of the module 

are used to set baud rate 

and node address. 

Address x10

Baud rate

Address x1

Setting Baud Rate (kbit/s)

0

20

1

50

2

125

3

250

4

500

5

800

6

1000

7

Auto

8, 9

Not available

Allowed node address range is 1 - 127. 

Addresses 1 - 99 are available using 

the address rotary switches.

To set e.g. node address 42, set 

the left address switch to 4 and the 

right address switch to 2. Cover the 

switches with the enclosed switch cov-

ers to ensure EMC compliance.

The Anybus X-gateway CANopen is certified for network compliance. 

For information contact www.anybus.com or www.can-cia.de.