6-17
Programming the SLCnet Card,
Continued
Step 3. Edit Each Point’s
Point Type
Edit an SLCnet point’s Point Type as follows:
1.
Move to the line corresponding to the SLCnet point whose point type you want to change
and double click on the Point Type field.
2.
Select the appropriate Point Type. Refer to the Monitor Point Type descriptions in
Appendix A for detailed information on SLCnet point types.
Note: Do not use the PC Programmer to change the point type of a suppression release point;
doing this causes the PC Programmer to change the point type back to its default setting. To
change the point type of a suppression release point, you must use the front panel programmer.
Step 4. Set Single
Station Mode (Detectors
with Sounder Bases
Only)
LIFEalarm devices with sounder bases default to Single Station mode. Single station has the
following effect.
•
Sounder activates when the associated sensor is above its alarm threshold.
•
Sounder silences when sensor is below its alarm threshold.
•
Alarm remains at panel until reset is performed.
Follow these steps to enable or disable Single Station mode for a specific point.
1.
Double click on the point's Mode field.
Two choices appear. One choice is blank (disables Single Station mode) and the other
choice is "Single Station" (enables Single Station mode).
2.
Select the appropriate mode.
To globally disable Single Station mode, use the front panel programmer interface (System
Options menu).