3-2
Connecting Serial Cable and Setting Serial Parameters
Overview
This section describes:
•
Connecting the serial cable (Part No. 431206) between the PC on which the programmer
software is installed and the AUTOPULSE Z-28 FACP's service port.
•
Setting PC Programmer serial communication parameters.
•
Setting the baud rate on the AUTOPULSE Z-28 FACP.
Step 1. Connect the
Serial Cable
Connect the (Part No. 431206)
serial cable between a free serial port on the service PC and the
service port of the AUTOPULSE Z-28 FACP, as follows:
1.
Locate the PC within 6 feet of the AUTOPULSE Z-28 FACP and connect the end shown
in Figure 3-1 to the PC. Make sure that the red stripe is aligned to the left as you connect
the cable.
2.
Connect the other end to the service port on the AUTOPULSE Z-28 FACP.
Figure 3-1. Connecting Serial Cable
Step 2. Set PC
Programmer
Communication
Parameters
The PC Programmer software requires you to specify settings for the following serial
communication parameters.
•
Port = COMx
•
Baud = 9600 or 19200 (recommended)
•
Parity = None
•
Stop Bits = 1
Continued on next page
•
Data Bits =8
Align the red stripe
to the left.
9-pin connector