Control Point Types,
Continued
A-7
RWATER
Waterflow signal - on until reset.
SIGNAL
Generic Alarm Signal - on until reset. Used for any signaling device (such as an audible or
visible notification appliance) that is required to be on until reset. Points assigned with this
type operate on general alarm.
SSIGNAL
Alarm signal - on until silence. Used for any signaling device (such as an audible or visible
notification appliance) that is required to be on until reset. Points assigned with this type
operate on general alarm.
SUPREL
Suppression release output.
Continued on next page
Circuit Status
LCD Display
System Status
ON
Signal Circuit
ON
OFF
Signal Circuit
OFF
Signal Circuit
CODING
Disabled TBL
Signal Circuit
TROUBLE
OFF AUTO TBL
Visual
TROUBLE
Circuit Status
LCD Display
System Status
ON
Signal Circuit
ON
OFF
Signal Circuit
OFF
Signal Circuit
CODING
Disabled TBL
Signal Circuit
TROUBLE
OFF AUTO TBL
Signal Circuit
TROUBLE
Circuit Status
LCD Display
System Status
Normal
Signal Circuit
ON
Normal
Signal Circuit
OFF
Signal Circuit
CODING
Disabled TBL
Signal Circuit
TROUBLE
OFF AUTO TBL
Signal Circuit
TROUBLE
Circuit Status
LCD Display
System Status
Normal
Signal Circuit
ON
Normal
Signal Circuit
OFF
Signal Circuit
CODING
Disabled TBL
Signal Circuit
TROUBLE