Control Point Types,
Continued
A-5
QALERT
NACnet Non-Addressable signal. QALERT device type has no automatic operation. All
operations for this device type must be programmed with Custom Control.
SQALERT
SQALERT device type automatically turns on the designated circuit on alarm detect (general
alarm), issues the horn silence command upon Alarm Silence, and turns off the circuit at the
completion of System Reset. Any point programmed with the SQALERT point type is not
available for use in Custom Control programming.
RELAY
Generic relay - no default operation. Used for any relay application that is not defined by a
specific point type.
RELISIG
Releasing investigation signal for NYC abort. Turns ON during the 90-second investigate time
after abort. Turns OFF when investigate timer expires.
Note: If RELISIG is assigned to a point that is not configured for NYC abort, the RELISIG
point will have No Operation.
RELSIG
Suppression release audible signal.
Uses programmed cadence for first stage alarms. Uses 120
bpm March Time during automatic or manual delay countdown. ON STEADY when agent is
released; OFF on reset.
Continued on next page
Circuit Status
LCD Display
System Status
ON
Auxiliary Relay
ON
OFF
Auxiliary Relay
OFF
Auxiliary Relay
CODING
Disabled TBL
Auxiliary Relay
TROUBLE
OFF AUTO TBL
Auxiliary Relay
TROUBLE
Circuit Status
LCD Display
System Status
ON
Release Investigate
ON
OFF
Release Investigate
OFF
Release Investigate
CODING
Disabled TBL
Release Investigate
TROUBLE
OFF AUTO TBL
Release Investigate
TROUBLE
Circuit Status
LCD Display
System Status
ON
Release Investigate
ON
OFF
Release Investigate
OFF
Release Investigate
CODING
Disabled TBL
Release Investigate
TROUBLE
OFF AUTO TBL
Release Investigate
TROUBLE