DCU20
User Manual rev. 19
Page 22/29
5.2.28 Relay 1 (Ready)
Used to configure the behavior of the
Relay 1
contact. Click OK and then follow the
instruction on the screen to define the polarity and event associated with the relay.
See §3.1.3 for more details.
5.2.29 Relay 2 (Backup)
Used to configure the behavior of the
Relay 2
contact. Click OK and then follow the
instruction on the screen to define the polarity and event associated with the relay.
See §3.1.3 for more details.
5.3 Info
While in the info menu, use the UP/DOWN KEY to navigate through the menu items.
5.3.1 Firmware version
Shows the current firmware version. Using the freely available
POWERMASTER
software is possible to upgrade the firmware with the latest available version.
5.3.2 Serial
Shows the device serial number (S/N). This serial number corresponds to the S/N
shown on the device label.
5.3.3 Name
Shows the device name. Using the freely available
POWERMASTER
software is
possible to modify the device name. The default name is DCU-20.
5.3.4 Power ON cycles counter
Shows the Power ON cycles counter, which is incremented by 1 every time the
device is powered ON.
5.3.5 Operating time
Shows the device operating time. The counter shows the hours of operation (device
powered) since the manufacturing.
22
DCU20_1680-21539-0006-E-1117