Andover Controls Corporation
i
TOC
CMX 240 Series ControllerInstallation Guide
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Page 1: ...Andover Controls Corporation i TOC CMX 240 Series Controller Installation Guide Technical Manuals Online http www tech man com firealarmresources com...
Page 2: ...Massachusetts 01810 All Rights Reserved Published by the Engineering Department at Andover Controls Corporation IMPORTANT NOTICE This product is subject to change without notice This document does not...
Page 3: ...the various CMX controllers It first presents site preparation informa tion and then step by step installation instructions We recommend you read Infinity Network Configuration Guide to plan your enti...
Page 4: ...iv CMX 240 Installation Guide Technical Manuals Online http www tech man com firealarmresources com...
Page 5: ...ly Cables 6 Lightning Protection 6 Building Ground Requirements 6 Inspecting the Ground 7 Environmental Requirements 8 Laying Out the Site Setup 8 Installing the CMX 240 Series Controller 9 Unpacking...
Page 6: ...cting the Battery 24 Interpreting Status Lights Inside Cabinet 25 Custom Port Status Lights 25 Communication Status Lights 25 Infinet Status Lights 26 Modem Power Light 27 System Activity Status Light...
Page 7: ...iring 19 Figure 7 Attaching the TankNet and Probe Power Supply Cables 20 Figure 8 Diagram of Safety Barrier Connection 22 Figure 9 Custom Port Status Lights 25 Figure 10 Communication Status Lights fo...
Page 8: ...Number of Infinet Controllers Allowed on Various CMX 240s 5 Table 2 AC Input Voltage Selection 14 Table A 1 Pinouts for RS 232 Comm Port with Male DB25 Connector to Terminal A 1 Technical Manuals Onli...
Page 9: ...CMX you can program the Infinet controllers This manual covers the following Site System Setup Requirements Installing the CMX 240 series controller Connecting to the Infinet Connecting to the TankNet...
Page 10: ...generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions in this manual may cause harmful interference to radio communications Operation...
Page 11: ...r they should be performed by Andover Controls Corporation or an authorized representative of Andover Controls Corporation For information contact Andover Controls at 300 Brickstone Square Andover Mas...
Page 12: ...t the modem is not required If you order any CMX 240 with the Infinity modem the modem is already installed If you order any CMX 240 without a modem and then add the Infinity modem later refer to the...
Page 13: ...connected to ground and the next conductor Number of Infinet Controllers on CMX Infinet You can have up to 64 Infinet controllers on a single CMX Infinet Table 1 shows the various model numbers and t...
Page 14: ...stall lightning arresters for Infinet to prevent electromagnetic disturbances Use lightning arresters at each point where Infinet cable enters or exits a building Use the following arrester Two pair g...
Page 15: ...than poorly grounded electrical systems a poor ly grounded building tries to reach ground through the Andover Controls system The surge of current can destroy electronic compo nents on the controller...
Page 16: ...MX 240 series controller on an Infinet You connect a terminal to the CMX You cannot connect an LBUS to a CMX 240 series controller You can not have an Infinity CX 9000 controller on the same Infinet w...
Page 17: ...ollowing parts CMX 240 Series Controller Cabinet provided or other enclosure Modem optional AC Power Cable Infinet Cable TankNet Cable and Intrinsic Safety Barriers optional for connecting TankNet Pro...
Page 18: ...s in the CMX cabinet or boards A metal shaving could easily short circuit the electronics 1 Pull the cable for a terminal or printer through the opening on the left side of the cabinet 2 Pull cables f...
Page 19: ...1 Figure 1 Backplate with Dimensions and Eyelets for Mounting CMX 240 8 550 4 275 90 6 575 13 150 14 25 11 50 45 4 Places 1 58 11 72 03 12 54 05 55 23 REF 2 000 015 Technical Manuals Online http www t...
Page 20: ...ERY CLEAR USE COPPER CONDUCTORS ONLY F2 3A 250V SLOW BLOW NEU HOT GND AC INPUT E7 E5 E2 E6 E2 E2 E4 E1 E1 E5 MODEM POWER F5 2A THIS DEVICE COMPLIES WITH PART 15 OF AC POWER F2 3A 250V SLOW BLOW MEMORY...
Page 21: ...ise the controller could malfunction 2 Notice that the three wires at the end of your AC cable are green white and black 3 Place the green wire under the metal plate behind the top screw labeled GND 4...
Page 22: ...the voltage from 115 V to 230 V proceed as follows 1 Remove the jumper from E3 to E5 2 Leave the jumper E2 to E4 as it is 3 Disconnect the jumper end from E1 and move it to E5 so it jumpers P2 to E5 T...
Page 23: ...preset for you to connect either a terminal or Infinity modem to COMM1 and COMM2 can be connected to a printer terminal com puter or modem by changing the port mode in the software COMM1 and COMM2 ca...
Page 24: ...E5 E2 E6 E2 E2 E4 E1 E1 E5 MODEM POWER F5 2A THIS DEVICE COMPLIES WITH PART 15 OF AC POWER F2 3A 250V SLOW BLOW MEMORY SHLD COM 26V 26V RD TD RTS RD TD RTS RD TD RD TD SERVICE PORT THE FCC RULES OPERA...
Page 25: ...the cable into the terminal port Connecting to the Infinity Modem If you are adding an Infinity modem you must install the Infinity modem before you connect it to the controller Refer to the Infinity...
Page 26: ...iring Infinet to the CMX 240 You wire the beginning of Infinet to all Infinity CMX 240 controllers After that you wire the Infinet to each Infinet controller Note You must use shielded cables for Infi...
Page 27: ...in place 6 Slip the second usually black wire from each Infinet cable under the screw labeled with a minus sign middle and tighten the screw down on them 7 Slip the shields from the incoming and outgo...
Page 28: ...the screw labeled with a minus sign and tighten the screw down on the wire 5 Tie back the shield 6 Read the following section about safety barriers and then wire them Wiring Probe Power Supply To conn...
Page 29: ...n contact MTS Systems Corporation at the following address MTS Systems Corp Sensor Division P O Box 13218 Research Triangle Park NC 27709 919 677 0100 Order Number 0592 550164 Revision B To reduce the...
Page 30: ...ect the power supply cable to any CMX 240 controller you wire the other end to the safety barrier Figure 8 is an illustration of the safety barrier connection Figure 8 Diagram of Safety Barrier Connec...
Page 31: ...7 If you have a TankNet be sure the TankNet safety barriers and probes are properly connected If you have completed all previous sections in this manual and installed all Infinet controllers you are n...
Page 32: ...the bat tery The battery 6 V lead acid battery is to the lower left in the cabinet You must connect the red and black wires hanging from the right side of the CMX 240 board to the battery as follows 1...
Page 33: ...m port The different colored lights flash to indicate the following TD Yellow Flashes when the custom port is transmitting data RD Green Flashes when the custom port is receiving data 26V Red Lights u...
Page 34: ...ting data RD Green Flashes when the custom port is receiving data RTS Red Lights up to indicate equipment modem terminal printer is on line Infinet Status Lights There are two Infinet status lights to...
Page 35: ...Figure 12 shows how the lights appear Figure 12 System Activity Status Lights All these lights except of course the ERROR light turn on when the power comes up The lights blink to indicate activity T...
Page 36: ...ting the Andover Controls Service Tool The SERVICE PORT on the lower left corner of the controller is to connect the Andover Controls Service Tool to any CMX 240 The ser vice tool will access all Infi...
Page 37: ...standard 25 pin ribbon cable for connect ing a modem to either a controller or a terminal However to connect any terminal to a controller you should use a cable with the required pinouts This appendix...
Page 38: ...erminal a To and From are in relation to the Infinity CMX 240 controller Modem means it is required for the modem Table A 1 Pinouts for RS 232 Comm Porta with Male DB25 Connector to Terminal Pin Numbe...
Page 39: ...necting to VT 100 Connecting to Controller Female End Female End 2 3 5 2 3 IBM AT 9 pin Connecting to Connecting to Controller 7 Female End Female End Modem Connecting to Connecting to Controller 2 3...
Page 40: ...A 4 CMX 240 Series Installation Guide Technical Manuals Online http www tech man com firealarmresources com...
Page 41: ...probe DIP switch so that you can determine the point channel number for each tank probe The DIP switch is located inside the probe head For details on how to access the DIP switch refer to the MTS in...
Page 42: ...override the power supply 3 Set switches 4 through 9 to the address that corresponds to the channel number of the probe Figure B 2 shows the address switch settings for the tank probe channels 1 thro...
Page 43: ...ON 1 2 3 4 5 6 7 8 9 ON Channel 1 Channel 2 1 2 3 4 5 6 7 8 9 ON 1 2 3 4 5 6 7 8 9 ON Channel 3 Channel 4 1 2 3 4 5 6 7 8 9 ON 1 2 3 4 5 6 7 8 9 ON Channel 5 Channel 6 Address 0 Address 1 Address 2 A...
Page 44: ...Hardware Installation B 4 CMX 240 Series Installation Guide Technical Manuals Online http www tech man com firealarmresources com...
Page 45: ...tions port COMM1 use 15 COMM2 15 computer connecting 17 configuration planning 8 controller dimensions 3 CPU light inside 27 D dimensions cabinet 3 controller 3 E ERROR light inside 27 F features uniq...
Page 46: ...ng required to ship for 9 requirements parts 9 RS 232 port pinouts A 2 S safety barrier connection 22 SCAN light inside 27 service port location of 15 purpose of 28 shields for Infinet cable connectin...
Page 47: ...MX 240 Installation Guide Index 3 W wiring connecting Infinet cable 19 correct wire gauge for ground 7 intrinsic safety barriers 21 Technical Manuals Online http www tech man com firealarmresources co...
Page 48: ...Index 4 CMX 240 Installation Guide Technical Manuals Online http www tech man com firealarmresources com...
Page 49: ...30 3001 391 CMX 240 Series Controller Installation Guide Rev D Technical Manuals Online http www tech man com firealarmresources com...