NOVUS AUTOMATION
44/85
13.1.5.1
LOGS
•
Log Data:
Enables or disables the device data logging.
•
Log Interval:
Allows you to select the frequency, in seconds, with which an acquisition must be made and logged in the memory.
○
Minimum Range:
■
1 second - if no channel is configured to operate on average
■
10 seconds - if a channel is configured to operate on average
○
Maximum Range:
18 hours.
13.1.5.2
START MODE
•
Immediate Start:
Allows logs to be started shortly after the device is reconfigured.
•
Date/Time:
Allows you to set the date/time when the logs are to be started.
•
By Keyboard:
In a screen in the display, you can change the logs status to
enabled,
which start the logs (in case they had not been started
yet).
•
By Digital Input:
Allows logs to be initiated from the digital input. This parameter is available if the digital input is enabled and configured in the
"Logs Control" mode. This way, the logs will be started the moment the digital input is triggered. The log edge shall be configured in the digital
input parameters.
•
By Software:
Allows logs to be started using an
NXperience
command.
•
Daily:
It allows the logs to be started every day and at the configured time. The "Daily" log start mode also requires "Daily" log end mode.
•
By Alarm:
Allows logs to be started from a specific alarm.
13.1.5.3
STOP MODE
•
Non-Stop:
Allows logs to continue indefinitely. When filling the memory, the oldest data will be deleted so that the most recent ones can be
saved.
•
Date/Time:
Allows you to set the date/time when the logs are to be ended.
•
By Keyboard:
Allows you to change logs status to
disabled
on a screen in the display by instantly closing the logs.
•
By Digital Input:
Allows logs to be paused from the digital input. This parameter is available if the digital input is enabled and configured in the
"Logs Control" mode. This way, the logs will be paused the moment the digital input is triggered. The log edge shall be configured in the digital
input parameters.
•
By Software:
Allows logs to be ended using an
NXperience
command.
•
Daily:
It allows the logs to be ended every day and at the configured time. The "Daily" log start mode also requires "Daily" log end mode.
•
By Alarm:
Allows logs to be stopped from a specific alarm.
The combinations allowed for starting and ending logs are as follows:
START MODE
STOP MODE
Immediate
Non-Stop or Date/Time or Keyboard or Software or Alarm
Date/Time
Non-Stop or Date/Time or Keyboard or Software or Alarm
Digital Input
Non-Stop or Digital Input
Keyboard
Non-Stop or Keyboard
Software
Non-Stop or Software
Daily
Daily
Alarm
Non-Stop or Alarm
Table 15 –