General
Input Frequency

45 - 65 Hz

Noise on Input

< 50 milli-Volts

Noise on Output

< 50 milli-Volts

Transient Response

< 1 V for 50% surge

Efficiency

> 80 % @ maximum output

Temp. Range

-25 to +40 deg. C @ maximum output

Isolation

Input-Output & Input-Case 1500 Vdc

Output-Case 500 VDC (1500Vdc @ 48 V Out)

Isolation

Output-Case 500 VDC (1500Vdc @ 48 V Out)

Length

14.5 in / 36.8 cm

Width

10.2 in / 25.9 cm

Height

5.5 in / 14.0 cm

Clearance

1 Inch (2.5 cm) all around

Material

Marine Grade Aluminum

Finish

Black Powder Epoxy

Fastenings

18-8 Stainless

Weight

12 lb / 5.5 kg

Summary of Contents for FBCS-2K-110-36

Page 1: ...Installation Operation Manual FBCS 2K Power Supply 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 1 800 668 3884 US CANADA www analyticsystems com...

Page 2: ...2 Copyright 2005 2013 Analytic Systems Ware 1993 Ltd...

Page 3: ...D AC POWER CORD CONNECTION INSTRUCTIONS The plug must be plugged into an outlet that is properly installed and grounded in accordance with al local codes and ordinances DANGER Never alter AC cord or p...

Page 4: ...ed 1 0 volts above or below the standard output voltage The model PWS1000 Power Supply supplies either 12 24 or 48 VDC from a 110 or 220 VAC power source High quality digital meters can be added facto...

Page 5: ...put Frequency 45 65 Hz Noise on Input 50 milli Volts Noise on Output 50 milli Volts Transient Response 1 V for 50 surge Efficiency 80 maximum output Temp Range 25 to 40 deg C maximum output Isolation...

Page 6: ...nd Green Yellow Ground All connections should be made inside an appropriate junction box The maximum current draw from the 110 VAC supply is 14 6 amps so a 20 amp circuit breaker should be used in the...

Page 7: ...equiped with the optional output isolation diodes To confirm that your unit has these diodes use an ohmmeter to measure the resistance between the two positive output terminals If the diodes are pres...

Page 8: ...at the output voltage is below normal because The current demanded by the devices connected to the unit exceeds the maximum output current rating thereby causing the output voltage to drop to maintain...

Page 9: ...the cover and locate J10 It will be next to the relay K1 as is shown in the above diagram Simply move the jumper to the desired position as is shown in the above diagram Replace the cover and re insta...

Page 10: ...the Purchas ers name address and telephone number b Call Analytic Systems at 800 668 3884 or 604 946 9981 and request a return material authorization number RMA c Return the defective part or unit alo...

Page 11: ...tability fitness for the ordinary purposes for which such goods are used or fitness for a particular purpose or any other obligations on the part of the Warrantor or its employees and representatives...

Reviews: