instruction manual

Axcess Control Cards

AXC-TEMP

Temperature Control Card and RTS-1 
Room Temperature Sensor

Summary of Contents for RTS1

Page 1: ...instruction manual Axcess Control Cards AXC TEMP Temperature Control Card and RTS 1 Room Temperature Sensor ...

Page 2: ...hird party or made by you for a third party This limitation of liability applies whether damages are sought or a claim is made under this warranty or as a tort claim including negligence and strict product liability a contract claim or any other claim This limitation of liabil ity cannot be waived or amended by any person This limitation of liability will be effective even if AMX Corporation or an...

Page 3: ...erature Sensor Table of Contents Product Information 1 Features 1 Pre Installation 3 Setting Fahrenheit or Celsius 3 Setting the Jumpers 3 Calibrating POTs 4 Connecting Multiple RTS1s 4 RTS1 Preparation 5 Wiring the RTS1 5 RTS1 Calibration 6 Testing the RTS1 7 Programming 9 ...

Page 4: ...ii AXC TEMP Temperature Control Card and RTS1 Room Temperature Sensor Table of Contents ...

Page 5: ...re sensing for the AXT TEMP Features The AXC TEMP features include Standard Axcess CardFrame slot size Settings for Fahrenheit or Celsius operation Control and power for up to four independent RTS1 units Measurement accuracy of 2 F 1 1 C Calibration for zero temperature deviation The RTS1 features include Precise temperature measurement from 5 to 128 F 29 2 to 106 9 C Connection to the AXC TEMP ca...

Page 6: ... Input voltage 12 to 18 VDC Current Draw 40 mA using four RTS1s 75 mA Temperature range 0 0 F to 250 F 0 0 C to 106 9 C Accuracy 2 F 1 1 C Resolution 10 bit 1024 steps over range RTS1 Weight 3 2 oz 91 grams Dimensions 4 5 x 2 75 x 9 114 mm x 70 mm x 23 mm Enclosure Metal off white finish Resolution 10 bit 1024 steps over range Temperature range 20 5 F to 250 F 29 2 C to 106 9 C ...

Page 7: ...ower on the system or reinsert the card into the CardFrame The default setting is Fahrenheit F 1 Set each jumper JP1 JP4 on the card for either Fahrenheit or Celsius 2 Set all calibration POTs to zero Each POT is a 25 turn POT Full counter clockwise is a 4 variance and full clockwise is a 4 variance 3 Insert the card into the desired Axcess CardFrame slot It is not necessary to disconnect power to...

Page 8: ...g for each POT pointer is 0 The table below describes the POT calibration for CH 1 CH 4 Connecting Multiple RTS1s FIG 5 shows the pinout for the AXC TEMP when connecting multiple RTS1s Calibration POTs CH1 CH4 POTs Description R1 Offsets input CHAN1 by 4 to 4 degrees R8 Offsets input CHAN 2 by 4 to 4 degrees R2 Offsets input CHAN 3 by 4 to 4 degrees R9 Offsets input CHAN 4 by 4 to 4 degrees R33 St...

Page 9: ... temperature changes by a half degree If the panel does not have a display check the variables in Axcess Wiring the RTS1 Use Belden 8723 or equivalent cable When an application or code requires plenum rated cable use Belden 88723 or equivalent cable Call AMX Technical Support for any installations that require a wire run of more than 100 feet FIG 6 RTS1 circuit connections 2 75 69 9 mm w front cov...

Page 10: ...the reference thermometer near each sensor you are calibrating FIG 7 RTS1 to Axcess Cardframe connections Input White Green Drain Ground Black Power Red Input White Green Drain Ground Black Power Red Input White Green Drain Ground Black Power Red Input White Green Drain Ground Black Power Red Green Drain Black Ground Red Power White Output Green Drain Black Ground Red Power White Output Green Drai...

Page 11: ...ch RTS1 unit for a few seconds The temperature on the display panel should change If the temperature does not change 1 Check the wiring to each RTS1 unit that did not display a temperature change 2 Verify the AXC TEMP card is properly seated in the CardFrame Repeat the steps provided in the RTS1 Calibration section on page 6 if required ...

Page 12: ...Pre Installation 8 AXC TEMP Temperature Control Card and RTS1 Room Temperature Sensor ...

Page 13: ...ts the number to print with a decimal point The 12 clears the LCD screen DEFINE_DEVICE TEMP 16 DEFINE_VARIABLE TEMP_LEVEL1 TEMP_LEVEL2 TEMP_LEVEL3 TEMP_LEVEL4 DEFINE_START CREATE_LEVEL TEMP 1 TEMP_LEVEL1 CREATE_LEVEL TEMP 2 TEMP_LEVEL2 CREATE_LEVEL TEMP 3 TEMP_LEVEL3 CREATE_LEVEL TEMP 4 TEMP_LEVEL4 DEFINE_PROGRAM WAIT 10 SEND_STRING LCD 12 ITOA TEMP_LEVEL1 10 ITOA TEMP_LEVEL1 10 For additional inf...

Page 14: ...A BELGIUM BRAZIL CANADA CHINA ENGLAND FRANCE GERMANY GREECE HONG KONG INDIA INDONESIA ITALY JAPAN LEBANON MALAYSIA MEXICO NETHERLANDS NEW ZEALAND PHILIPPINES PORTUGAL RUSSIA SINGAPORE SPAIN SWITZERLAND THAILAND TURKEY USA ATLANTA BOSTON CHICAGO CLEVELAND DALLAS DENVER INDIANAPOLIS LOS ANGELES MINNEAPOLIS PHILADELPHIA PHOENIX PORTLAND SPOKANE TAMPA 3000 RESEARCH DRIVE RICHARDSON TX 75082 USA 800 22...