Installation Guide

CB-TP15 

Rough-In Box for 15" Wall/Flush Mount Touch Panels

Overview

Wall Mount panels (NXDs) are contained within a metallic outer housing (back 
box). This back box is 

not removed

 when installing the NXD into a CB-TP15 

Rough-In Box. The back box is 

only

 removed to gain access for the replacement 

of the Compact Flash component or upgrade to the VESA housing.
The CB-TP15 Rough-In Boxes are optional metallic boxes that are secured onto 
stud beams prior to the installation of a solid surface. Installation procedures and 
configurations can vary. 

Specifications 

WARNING

: INSTALLER, LEAVE A GAP BETWEEN THE STUD AND ROUGH-

IN BOX TO ACCOMMODATE THE DRYWALL/SHEETROCK. 
This gap allows the installation of the drywall/sheetrock after the Rough-In Box 
has been installed.

Note

: The most important thing to remember when mounting this Rough-In Box 

is that the mounting tabs must be mounted flush against the outside of the 
sheetrock. 

Pre-Wall Installation of the CB-TP15 Rough-In Box

1.

Fasten the CB-TP15 to a stud through the stud fastening holes, located on 
the inside of the Rough-In Box (FIG. 1), by using either nails or screws. 

2.

Remove any necessary wiring knockouts from the Rough-In Box (

C

 in 

FIG. 2) where the necessary cables are threaded through for connection to 
the touch panel.

3.

Thread the incoming RJ-45, Ethernet, and any other audio/video wiring 
through the knockouts. 

4.

Install the drywall/sheetrock before inserting the main NXD unit into the 
CB-TP15.

Installing a 15" NXD panel within a Rough-In Box

The Rough-In Box must be mounted prior to continuing this section. Verify that 
all necessary cables have been threaded through the knockouts on the Rough-In 
Box and the connections have been tested prior to installation of the touch panel.
1.

Remove the magnetic faceplate/bezel (

A

 in FIG. 2) from the main NXD unit 

(

B

 in FIG. 2) by gripping the faceplate and pulling with gentle outward force. 

2.

Verify the incoming RJ-45, Ethernet, USB, and any other audio/video 
cables have been properly threaded through the wiring knockouts (from 
their terminal locations) on the Rough-In Box. Leave enough slack in the 
wiring to accommodate any re-positioning of the panel.

3.

Connect all data and power wiring connectors to their corresponding 
locations along the side of the (un-powered) NXD touch panel. 

• Verify the terminal end of the power cable is not connected to a power

 supply before plugging in the 2-pin power connector.

• The USB connectors can be from either a USB extension cable, or 

 a wireless USB RF transmitter.

Note

: Don’t disconnect the connectors from the touch panel. The unit must be 

installed with the attached connectors before being inserted into the Rough-In 
Box.

4.

Test the incoming wiring by connecting the panel connections to their 
terminal locations and applying power. Verify the panel is receiving power 
and functioning properly to prevent repetition of the installation.

5.

Disconnect the terminal end of the power cable from the connected PSN 
power supply.

6.

Carefully slide the main NXD unit (

B

 in FIG. 2) into the Rough-In Box, so 

the Mounting Tab lies flush against the Rough-In Box (

C

 in FIG. 2).

7.

Insert and secure the four securing #4-40 Mounting Screws into their 
corresponding holes located along the sides of the NXD. 

8.

Replace the magnet faceplate (

A

 in FIG. 2) back onto the main NXD unit. 

Make sure to align the Microphone, Light, and PIR Motion sensor locations 
to their respective openings on the front bezel/faceplate.

9.

Connect the terminal RJ-45, Ethernet, and any optional audio/video wiring 
to their respective locations (outside the Rough-In Box) on either the AVB 
breakout box, Ethernet port, or NetLinx Master. 

10. Reconnect the terminal power connector on the PSN and apply power
    

CB-TP15 (FG032-10) Specifications

 Dimensions (HWD) • 13.48" x 14.18" x 3.49" 

• 34.24 cm x 36.00 cm x 8.85 cm

Included 
Accessories

Rough-In Box Installation Kit (SA2001-02) (

one kit per CB

)

• 4 Phillips pan-head (#4-40 x 0.375 Black) screws (80-0115)
• 4 Phillips pan-head (#4-40 x 0.625 Black) screws (80-0118)

Certifications

• cTUVus Listed

FIG. 1  

Screw locations for Rough-In Box attachment in a pre-wall installation

Drywall/

Stud

Knockouts should be located on the left-side of the

CB-TP15 Rough-In Box

Rough-In Box, alongside the connectors

Stud fastening holes

Use the four #4-40
Mounting Screws to 
secure the NXD to the 
Rough-In Box at these

sheetrock

Mounting tabs
for NXD panel should
be flush with the outside of the sheetrock

locations