1.2.1 CTRL Integrated Controller Panel designation 

The new family of 1RU nrgSMART panels are now available with an integrated controller, designated with a 
“CTRL” in the part number. This embeds a primary controller directly into the fuse panel, eliminating the need 
for a separate external controller, and provides 1:1 network connectivity to each independent nrgSMART 
power panel designated with CTRL. 

 

1)  Do not use the nrgNET cable to connect multiple CTRL panels together. 
2)  Do not use the nrgNET cable to connect a CTRL panel to an nrgCONTROL-BT external controller. 
3)  Do not use the nrgNET cable to connect a CTRL panel to an nrgBDFB-XLW controller. 

1.2.2 SENS Sensor Panel designation 

For customers that desire 1-point connectivity (1:N) for multiple panels, the new family of 1RU nrgSMART 
panels are available as sensor-only panels

, designated with a “SENS” in the part number.  Sensor-only panels 

must be connected via a serial cable to a controller for network communications.  This can either be a 
nrgSMART panel with an integrated controller (CTRL), or to a legacy nrgCONTROL-BT external controller, or 
to a nrgBDFB-XLW  

 

1.2.3 Legacy nrgSMART Compatibility 

 

 

 
The new nrgSMART architecture differs from our legacy nrgSMART architecture in one key area: the nrgNET 
serial link.  Please note these key differences: 
 

New architecture: 

  In a 1:N architecture, one nrgSMART CTRL panel can serve as a single network connection for 

up to 30 Sensor (SENS) panels. Sensor (SENS) panels contain all required nrgSMART sensing 
electronics but do not contain the controller electronics. 

  The nrgSMART electronics of Sensor panels are powered directly off the A and B feeds within 

each panel, allowing the panels to operate with standard alarming when installed and not 
connected to a controller. 

 

This is an improvement over legacy nrgSMART panels, which had their nrgSMART electronics 
powered through the nrgNET cable by the external controller (either nrgCONTROL-BT or within 
the nrgBDFB-XLW)

  The new architecture uses the same 5-pin nrgNET connector and cable, however, the two 

power conductors are not used. 

  The new architecture also allows the alarming to operate without the nrgNET cable connected 

as power is pulled from the A & B bus to power the alarm card. 

 

 

Compatibility with Legacy nrgSMART products (nrg100GMT10, nrg600BT10, nrg600BT08 models): 

Summary of Contents for nrgSMART CTRL

Page 1: ...nrgSMART Integrated Controller CTRL SENS versions System Configuration Guide...

Page 2: ...he data and communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We...

Page 3: ...ensor Panel designation 5 1 2 3 Legacy nrgSMART Compatibility 5 1 3 Specifications 6 Section Two Operation 7 2 1 Operation Guidelines 7 2 1 1 nrgSMART Connectivity CTRL Versions 7 2 3 Parts Accessorie...

Page 4: ...umes no liability from the application or use of these products Amphenol Network Solutions does not convey a license under its patent rights nor the patent rights of others This document and the produ...

Page 5: ...be a nrgSMART panel with an integrated controller CTRL or to a legacy nrgCONTROL BT external controller or to a nrgBDFB XLW 1 2 3 Legacy nrgSMART Compatibility The new nrgSMART architecture differs fr...

Page 6: ...d power rating 12V 18mA 0 22W 24V 20mA 0 48W 48V 30mA 1 44W Alarm wire size 24 AWG typical 26 to 20 AWG Terminals Wire wrap or mates with TE Connectivity 3 640428 3 Compliance Specifications UL Listed...

Page 7: ...are release See Figure 1 Figure 1 CTRL Panel Connectivity Ports 2 The integrated nrgSMART Controller is set to DHCP client by default Connect an ethernet cable from the network to the LAN port on fron...

Page 8: ...being monitored by the controller o Integrated Controller Name o nrgOS version o Number of active panels o IP address o Integrated Panel name o Integrated Panel serial number o Feed Current A and B o...

Page 9: ...Interface 5 The nrgNET serial connectors nrgTEMP connectors and dry contact alarm terminals are located in the rear center of the panel Refer to Figure 2 Figure 2 Rear Connections nrg240GT54 panel sho...

Page 10: ...eable Controller Card nrgSMART 400822 Replaceable Sensor Card nrgSMART 307607 Faceplate for Sensor Card nrgSMART 150158S E2 Faceplate for Controller Card nrgSMART 150619S E2 SENS to CTRL conversion co...

Page 11: ...2 ICES 003 Class A Notice Avis NMB 003 Class A This Class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme la norme NMB 003 du Canada ELECTROSTATI...

Reviews: