10.5 UPS Output (Alarm & Run Time) Menu
– 4
th
Major Sub-Menu
6D.Alarm & Run
Time Setup
Press the UP button to access this menu. This major sub menu allows the viewing and setting of various
UPS parameters, as follows:
The output over-current level
The output under-current level,
The output under voltage level,
Run time and
Shutdown on DI1
10.5.1 Output Over-Current Level Menu
OP OverCurrLevel
> 1.0 A <
Press the RIGHT button to gain access to this menu. This menu allows entry of the level of current that
will result in the Output Over-Current alarm being activated. The UP/ DOWN button
increments/decrements the setting in 0.1 Amp intervals. The minimum setting is 0.0 Amps, the
maximum is 2.5 Amps. Default setting 0.4A; Hysteresis is 20% of the current limit from Table 1.
The RIGHT button progresses to the next menu.
The LEFT button returns to the previous menu.
The ENTER button saves the setting into memory.
Press the ESC button to return to UPS Output Menu (fourth Major Sub-menu).
10.5.2 Output Under-Current Level Menu
OP UnderCurrLevel
> 0.7 A <
Press the RIGHT button to gain access to this menu. This menu allows entry of the level of current that
will result in the Output Undercurrent alarm being set. The UP/DOWN button increments/decrements the
setting in 0.1 Amp intervals. The minimum setting is 0.0 Amps, the maximum being 2.5 Amps. Default
setting 0.0A; Hysteresis is 20% of the current limit from Table 1.
The RIGHT button progresses to the next menu.
The LEFT button returns to the previous menu.
The ENTER button saves the setting into memory.
Press the ESC button to return to UPS Output Menu (fourth Major Sub-menu).