background image

ADVANCED WARNING

SY ST EMS

 

Apartment Module 
Installation Guide

 

Item Numbers: 226-0003 

 

MAN1570-2 

N1236

 

Page 1 

WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS 

Ampac Technologies Australia

 Tel: +61 8 9201 6100 

Europe

 Tel: +44 (0) 1302 833 522 

New Zealand

 Tel: +64 9 443 8072 

www.ampac.net

  

 

Description: 

The Apartment Module (AM) is a loop powered 
addressable device that helps reduce the costly 
consequences of an unwanted alarm 

An occupant is able to silence a local audible warning, 
activated by a local smoke detector, and allowing a 
preset time to investigate the cause of the alarm. Local 
smoke detectors can be connected directly to the AM 
(conventional) or connected to the addressable loop 
(addressable) and assigned to the AM. 

The local smoke detector is self resetting and if the 
smoke clears, then the system will return to normal. If 
the smoke remains, then the local audible warning will 
resound at the expiry of the preset timeout. A local 
smoke detector will NOT cause a general fire alarm. 

The fire system will go into general fire alarm (thus 
calling the brigade) if: 

  Any thermal detector has gone into alarm 

(conventional connected to the AM or addressable 
connected to the addressable loop) 

  Any smoke detector in common areas has gone 

into alarm 

  Any call point activated 

ConfigManager is programmed to identify the 
associations of AM’s with the local smoke detectors 
(conventional and addressable) and adjustment of the 
“Investigation” period.  

AM Features 

  Loop interface with Short Circuit Isolator (SCI) 

  On-board Hush Switch with integrated front panel 

Fire LED (red) and external hush input 

  Indicators: Poll / SCI LED (green – behind cover), 

Fault LED (yellow – behind cover)

 

  100V Line output with EOL monitoring 

  Conventional Zone circuit with selectable EOL 

Installation: 

Observe anti-static precautions at all times 

1. 

Two DIP switches are provided, SW2 for 
addressing (8 way) and SW1 for module options 
(4 way) as below. 

DIP SW1 

Name 

Operational Parameters 

1 Not 

used 

 

2 EOL  

Zone EOL 
selection 

2 off:    EOL = 10uF 
(default setting) 

2 on:    EOL = 6K2 

3 Ext. Hush 

Ext. HUSH 
Input 

ON for monitoring the 
External Hush Input 

4 Poll 

Poll LED 

ON for Poll LED operation 

2. 

Establish the operational criteria for the module 
and configure the FACP software accordingly 

3. 

Remove the white face plate and set the 
address and operational parameters via the dip 
switches 

4. 

All cabling should be run into a general purpose 
wall box and connected as 

per Figure 1

 

5. 

The AM is then screwed to the wall box and 
tested – replace the face plate once testing is 
complete 

Testing 

1. 

Prepare the most suitable situation for the 
installation to test the AM then create a local 
“alarm”  

2. 

The alarm indicator should illuminate when the 
alarm is recognised by the AM 

3. 

Check the silence function, the configured 
“Acknowledgement” and “Investigation” timing 

4. 

Introduce a fault condition eg 1. remove the “Ext. 
Hush” EOL, 2. check short circuit isolation 
operation. 

ADDRESS SWITCH

EOL, EXT HUSH,

POLL SELECTION

SWITCH

POLL LED

FAULT LED

ALARM LED

LOOP IN -VE

LOOP IN +VE

EXTERNAL "HUSH"

ZONE ( CONVENTIONAL DEVICES )

100V LINE

IN

OUT

-

+

-

+

-

+

-

+

-

+

+

+

-

-

100V LINE

TO SPEAKERS

EOL

47K

EOL

22K

4K7

NOTES:

#1 SELECTED EOL MUST BE A APPLIED

EVEN IF THE FUNCTION IS UN-USED

ZONE ( CONVENTIONAL DEVICES ) EOL

10uF ( SW1 / 2 OFF )

6K2   ( SW1 / 2 ON )

FAULT TESTING

1. SHORT/OPEN THE ZONE

2. REMOVE EACH EOL IN TURN

3. REMOVE THE 100V LINE IN

POLL/SCI FAULTS

1. OPEN THE LOOP

2. SHORT THE LOOP

 

Figure 1: Apartment Module general wiring 

Reviews: