AMK Solac 11252 DeltaSol_BX.monen.ind
d
|
96
Level 5
7
User code and short menu -
Adjustment values
The access to some adjustment values can be restricted via
a user code (customer). For safety reasons, the user code
should generally be set to the customer code before the
controller is handed to the customer!
1. Expert
0262
(Factory setting)
All menus and adjustment values are shown and all values
can be altered.
2. Customer
0000
The expert level is not shown, adjustment values can be
changed partly (see below)
Î
In order to restrict the access, enter 0000 in the menu
item
CODE
.
The display changes to the status level. If the adjustment
channel is selected afterwards, the short menu shown below
will be available. The short menu suits the selected system.
Î
In order to authorize the access, enter 0262 in the menu
item
CODE
.
Channel
Factory setting
Adjustment range
Description
TIME
12:00
00:00 23:59
Time
DT O
6
1.0 ... 50.0
Switch-on temperature difference store
DT F
4
0.5 ... 49.5
Switch-off temperature difference store
DT S
10
1.0 ... 50.0
Set temperature difference store
S MAX
60
4 ... 95
Store maximum limitation
DT1O
6
1.0 ... 50.0
Switch-on temperature difference store 1
DT1F
4
0.5 ... 49.5
Switch-off temperature difference store 1
DT 1S
10
1.0 ... 50.0
Set temperature difference store 1
S1MAX
60
4 ... 95
Store maximum limitation store 1
DT2O
6
1.0 ... 50
Switch-on temperature difference store 2
DT2F
4
0.5 ... 49.5
Switch-off temperature difference store 2
DT 2S
10
1.5 ... 50.0
Set temperature difference store 2
S2MAX
60
4 ... 95
Store maximum limitation store 2
LST2
ON
ON / OFF
Loading store 2 on
MAN1
Auto
Auto / ON / OFF / n LO / n HI Manual operation pump 1
MAN2
Auto
Auto / ON / OFF / n LO / n HI Manual operation pump 2
MAN3
Auto
Auto / ON / OFF / n LO / n HI Manual operation pump 3
MAN4
Auto
Auto / ON / OFF
Manual operation pump 4
CODE
0000
0000 / 0262
User code
Code