2.6
System layouts
System 1
Standard solar system with 1 store
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
Relay
Description
R1
Solar pump
R2
optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump
R3
R4
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT S
10 K
Set temperature difference
RIS
2 K
Rise
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL >
Collector
CEM
115°C
Collector emergency temperature
OCCO**
OFF
Option collector cooling
CMAX
95 °C
Maximum collector temperature
OCMI
OFF
Option collector minimum limitation
Sensor/Ter-
minal
Designation Description
S1
TCOL
Temperature collector
S2
TSTB
Temperature store base
S3
Optional sensor for measurement
purposes or options
S4
S5
VFS
RPS
V40
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
R1
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in