Level 5
DT3 / DT3O
Switch-on temperature diff.
Adjustment range
: 1.0 ... 50.0 K
in steps of 0.5 K
Factory setting: 6.0 K
DT3 / DT3F
Switch-off temperature diff.
Adjustment range: 0.5 ... 49.5 K
in steps of 0.5 K
Factory setting: 4.0 K
DT3 / DT3S
Set temperature diff.
Adjustment range: 0.5 ... 50.0 K
in steps of 0.5 K
Factory setting: 10.0 K
DT3 / RIS3
Rise
Adjustment range: 1 ... 20 K
in steps of 1 K
Factory setting: 2 K
Heat exchange function / solid fuel boiler / return
preheating
The heat exchange function is used for transporting heat
from store 1 to store 2.
Additionally, minimum and maximum temperature limits and
the corresponding switch-on and switch-off differences can
be set for the independent temperature differential control.
Both switch-on and switch-off temperature differences
DT3O
and
DT3F
as well as the set temperature difference
DT3S
and rise
RIS3
are valid.
Minimum temperature limitation
Maximum temperature limitation
DT3 / MIN3O
Switch-on temperature
Adjustment range
:
0.0 ... 89.5 °C
Factory setting
: 5 °C
DT3 / MIN3F
Switch-off temperature
Adjustment range
:
0.5...90.0 °C
Factory setting
: 10 °C
ARR= 2, 11, 16, 17, 18
MIN3O 5,0 °C
MIN3F 10,0 °C
ARR= 8, 13, 26
MIN3O 60,0 °C
MIN3F 65,0 °C
DT3 / MAX3O
Switch-on temperature
Adjustment range
: 0.5...95.0 °C
Factory setting
: 60 °C
DT3 / MAX3F
Switch-off temperature
Adjustment range:
0.0 ... 94.5 °C
Factory setting: 58 °C
If the adjusted value
MAX3O
is exceeded, the relay will
be switched off. If the temperature falls below the adjusted
value
MAX3F
, the relay will be energised.
Reference sensor:
S3 for ARR 8, 13, 26 (TSTT)
S4 for ARR 2, 11, 16, 17, 18, 24 (TST2B)
If the temperature falls below the adjusted value
MIN3O
,
the relay will be switched off. If the adjusted value
MIN3F
is exceeded, the relay will be energised.
Reference sensor:
S3 for ARR 8, 13, 26 (TSFB)
S4 for ARR 2, 11, 16, 17, 18, 24 (TSTT)