Level 5
Time period - switch-on condition
LLOGI/ODB/tDTO
Time period - switch-on
condition
Adjustment range: 1 ... 100 s
in steps of 1 s
Factory setting: 60 s
The parameter
tDTO
is used for adjusting the time period
during which the switch-on condition
DT O
must be per-
manentely fulfi lled.
Stabilisation
LLOGI/ODB/tSTB
Stabilisation
Adjustment range:
1.0 ... 15.0 min
in steps of 0.5 min
Factory setting: 2 min
The parameter tSTB is used for adjusting the time period
during which the switch-off condition
DT F
will be ignored
after the fi lling time has ended.
LLOGI/ODB/tFLL
Filling time
Adjustment range:
1.0 ... 30.0 min
in steps of 0.5 min
Factory setting: 5.0 min
The fi lling time can be adjusted using the parameter
tFLL
.
During this period, the pump runs at 100 % speed.
Filling time
By means of this function, store loading continues after the
temperature difference between the collector and the store
has fallen below the switch-off difference. Store loading is
stopped if the adjusted
∆
T overrun difference between fl ow
and return sensor is underrun.
LLOGI/OOVRU
Selection: ON / OFF
Factory setting: OFF
LLOGI/DTOVR
Adjustment range: 0.0 ... 20.0 K
Factory setting: 5.0 K
Overrun
Note:
The overrun function is only available, if both
Grundfos sensors (VFS and RPS) are used.
Booster function
LLOGI/ODB/OBST
Booster function
Adjustment range: ON / OFF
Factory setting: OFF
This function is used for switching on a second pump when
fi lling the solar system. When solar loading starts, R3/R4 is
energised in parallel to R1. After the fi lling time (
tFLL
) has
ended, R2 is switched off.
Note:
The booster function is available in systems 1, 3,
8, 9, and 10 only.