The controller compares the temperatures at the collector
sensors S1 and S5 to the store temperatures at the sensors
S2 and S3. If one of the measured temperature differences is
higher than the adjusted switch-on temperature differences,
the corresponding pump (R1, R2) or both pumps will be
activated and the corresponding store zone will be loaded
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
26
System
LOAD1 >
Loading 1
DT1O
4 K
Switch-on temperature difference 1
DT1F
2 K
Switch-off temperature difference 1
DT1S
10 K
Set temperature difference 1
RIS1
2 K
Rise 1
S1MAX
75 °C
Store maximum limitation 1
SMXS1
2
Sensor store max 1
LOAD2 >
Loading 2
DT2O
4 K
Switch-on temperature difference 2
DT2F
2 K
Switch-off temperature difference 2
Sensor/Ter-
minal
Designation
Description
S1
TCOL1
Temperature collector 1
S2
TSTB
Temperature store base
S3
TSTT
Temperature store top
S4
TSFB
Temperature solid fuel boiler
S5
TCOL2
Temperature collector 2
VFS
Optional sensor for measurement
purposes or options
RPS
V40
Relay
Description
R1
Solar pump collector 1
R2
Solar pump collector 2
R3
Loading pump solid fuel boiler
R4
3-port valve store top/base
System 26
Solar system with east-/west collectors, store loading in layers and afterheating with solid fuel boiler
up to the adjusted maximum temperature via the valve (R4).
The priority logic effects prior loading of the upper zone
of the store.
With another temperature differential function (S4/S3),
afterheating of the store can be carried out with a solid
fuel boiler (R3).