AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
S
YSTEM
C
ONFIGURATION AND
S
ET
-U
P
The AN-3100D Annunciator is already factory configured per the model number.
Most of the configuration of the system is made using software, however some
settings such as relay contact arrangement (Form A or Form B) needs to be
configured by the user. The default configurations are specified below:
Item Default
Setting
Configuration
Method
Inputs
N.O. (normally open), N.C. (normally
closed) Field Contact Inputs
N.O. Software
or
Hardware *
Field Contact Voltage
(12, 24, 48, 125VDC, 120VAC)
OR
(24-125VDC)
Factory
Configured
Per Model
Number
Hardware
Common FCV (field contact voltage)
or Isolated FCV
Hardware
Input Module Address Setting
Hardware
Operational Sequence (A, M, etc)
Software
Sequence Grouping
1 group
Software
Input Response
50 msec
Software
Critical/Non-Critical Assignment Non-Critical
Software
Optional
Repeat Relays
Form A (normally open), Form B
Contacts (normally closed)
Form A
Hardware
Form C Contacts (SPDT)
Factory
Configured
Per Model
Number
Hardware
Energized or De-Energized Relays
De-Energized Software
Repeat Relay Operation
Follows Input
Software
CSM Functions Auxiliary Contact Output Type
(Form A, Form B)
Form A
Hardware
Auxiliary Contact Output Mode
(Energized or De-Energized)
De-Energized Software
Auxiliary Contact Output Operation
(Horn, Reflash, Fault, Watchdog,
Power Monitor, Ground Fault)
Critical Horn
& Non-Critical
Horn
Software
Other system-wide functions
None
Selected
Software
Serial
Communication
Module
RS-232 , RS-485
RS-232
Software
RS-485 Termination Jumper
Out
Software
Flash Synchronization (master/slave) Master
Hardware
* NO/NC Field Inputs can be configured via the software or hardware, but
not both. Choose one method only.