Installation on a Combustible Floor

If the appliance is to be installed on a combustible 
floor or a combustible floor covering, it must be 
installed on a 1” thick non-combustible millboard 
floor protector or a durable equivalent. The pad must 
be installed beneath the unit, extending 16” (U.S.) on 
the side equipped with a door, and 8” on all other 
sides. The pad must cover any horizontal chimney 
connector runs and extend 2” beyond each side. 

Alternate Floor Protection:

An easy means of determining if a proposed alternate 
floor protector meets requirements listed in the 
appliance manual is to follow this procedure:

1)

 Convert specification to R-value:

2)

 Determine the R-value of the proposed alternate 

floor protector.

3)

 If the overall R-value of the system is greater 

than the R-value of the specified floor protector, the 
alternate is acceptable.

Example:
The specified floor protector should be 3/4-inch thick 
material with a k-factor of 0.84.  
The proposed alternate is 4” brick with a C-factor of 
1.25 over 1/8” mineral board with a k-factor of 0.29.

Step (a):

Use formula above to convert specification to R-value.  
R = 1/k x T = 1/0.84 x .75 = 0.893

Step (b):

Calculate R of proposed system.
4” brick of C=1.25, therefore Rbrick=1/C=1/1.25= 0.80
1/8” mineral board of k = 0.29, therefore Rmin.bd. = 
1/0.29 x 0.125 = 0.431
Total R= Rmineral board= 0.8 + 0.431 = 1.231

Step (c):

Compare proposed system R of 1.231 to specified 
R of 0.893.  Since proposed system R is greater than 
required, the system is acceptable.

Definitions:

2. Wall Protection 

Please see 

Illustration 3

 for clearances to walls. 

In some areas local codes may require thirty-six 
inches (36”) from a combustible, therefore it is very 
important that you check with local officials. If you 
need to place your unit closer to a combustible wall, 
some protection will be necessary. If an approved 
wall board is used this will reduce your clearance by 
two thirds (2/3); however, a one inch (1”) air space has 
to be between the board and the wall. If you have a 
ceiling flue hook-up, you will need protection from 
the floor to the ceiling if you do not meet the normal 
clearances. If you have a wall flue hook up, you will 
need wall protection at least twelve inches (12”) 
above the wall thimble. 

i

    R-value is given - no conversion is needed.

ii 

  k-factor is given with a required thickness (T) in    

      inches:  R = 1/k x T 

iii

  C-factor is given:  R = 1/C

i  

 Use the formula in step (1) to convert values not    

     expressed as “R”.

ii

  For multiple layers, add R-values of each                                            

    layer to determine the overall R-value.

Thermal conductance = C =       Btu              =      W    
                                                       (hr)(ft2)(ºF)          (m2)(ºK)

Thermal conductivity  = k =    (Btu)(inch)    =      W       =      Btu     
                                                          (hr)(ft2)(ºF)        (m)(ºK)      (hr)(ft)(ºF)

Thermal resistance       = R =    (ft2)(hr)(ºF)   =  (m2)(ºK) 
 

 

                 Btu                       W

Illustration 3

CLEARANCE TO COMBUSTIBLES

Appliance 

Clearances

Unprotected Surfaces

Side

(A)

Rear

(B)

Corner

(D)

Connector 

to  backwall 

(C)

Connector 

to wall  

(corner) (E)

Single wall 

connector

R 450

14 in

355 mm

16 in

406 mm

16 in

406 mm

16.75 in

425 mm

16.75 in

425 mm

NOTE: Alcove ceiling minimum height = 48 in

Convection cover (Side Heat Shields )

The AMESTI R- 450 has a cover of the combustion 
chamber for generating heat by convection. Also, this 
cover act like a heat shield incorporated in hardware. 
(Is not necessary to install other piece.)

AMESTI R 450 have refractory bricks just like show the 
Illustration 4

Illustration 4

15 refractory bricks: 7.1” x 2.3” x 0.8”

FREESTANDING PLACEMENT 

AND INSTALLATION 

The first problem you may encounter is getting your 
stove into your home -- all of our stove products are 
well constructed, which makes them rather heavy. 
Three to four adults can normally handle a unit, but 
we still recommend using a handcart. Never attempt 
to handle a heating product alone!!! The door and 
brick can be temporarily removed to lighten the unit 
(refer to Brick Layout). 

Chimney Connector Pipe 

 

The black pipe must be six inches (6”) in diameter and 
at least 24 gauge steel pipe. Do not use aluminum 
or galvanized steel pipe, as it will not withstand the 
extreme temperatures generated by the stove. Also, 
do not use single wall connector pipe as a chimney -- 
you must connect your stove to a chimney comparable 
to those listed earlier in this manual. The crimped end 
of your pipe should be inserted into the flue collar 
and, by doing this, all the pipe will be reversed. If 
you use this method the creosote will run back down 
the inside of your pipe and not out of the joints onto 
your stove. As a safety precaution, all joints should be 
sealed with high temperature silicone 

(AC-RTV3)

 and 

secured with sheet metal screws.

8

9

Summary of Contents for R 450

Page 1: ...h July 1990 Particulate emission standards Tested to UL 1482 2000 ULC S627 2000 OWNER S MANUAL MODEL NUMBER AMESTI R 450 Thank you for purchasing this product from a fine line of heating equipment fro...

Page 2: ...ite at www amesti cl for helpful information frequently asked questions parts accessory orders and more Technical Support 800 444 6742 OPERATION WHY THE CORRECT FLUE SIZE IS IMPORTANT 6 Draft is the f...

Page 3: ...amage caused by the malfunction of a stove due to improper installation Do not use makeshift methods or material which may compromise the installation The manufacturer will not be responsible for an a...

Page 4: ...or a single wall sheet steel chimney connector of minimum 24 gauge thickness with a minimum 2 in air space between the outer wall of chimney section and combustibles Minimum length of chimney section...

Page 5: ...k up you will need wall protection at least twelve inches 12 above the wall thimble i R value is given no conversion is needed ii k factor is given with a required thickness T in inches R 1 k xT iii C...

Page 6: ...tallation rigid 10 Maintain the required diameter flue for the entire installation 11 If you are connecting the stove to an old masonry flue besuretohaveitinspectedforcracksandgeneral condition Relini...

Page 7: ...nlet control until the fire is well established approximately 20 minutes being careful not to over fire 8 Readjust the air inlet control to the desired burn rate If excessive smoke fills the firebox o...

Page 8: ...ufacturer includes a steel handle with each fireplace This handle must be used to open and close the door and to move the air control lever The handle must be stored away from the fireplace to prevent...

Page 9: ...60 of the fuel value of dry seasoned wood will deposit creosote on the inside of the stove and along to inside of the chimney 4 What does dry seasoned wood mean and what is considered to be hardwood...

Page 10: ...his fireplace referring to the materials and manufacturing will be free of defects at the time of purchase The manufacturer extends the following warranties Five Year Period Steel and welded joints in...

Page 11: ...____ Dealer store Other ____________________________________________________ Where did you receive information about our product Please check one ___ Rec d info via phone ___ Dealer Name of dealer ___...

Page 12: ...16 Visitez notre site web www amesti cl pour des informations utiles questions fr quentes commande de pi ces accessoires et plus Assistance Technique 800 444 6742 FONCTIONNEMENT POURQUOI UNE TAILLECO...

Page 13: ...nsabledesaccidents dus au raccordement de l unit un syst me de chemin e d fectueux APPLICATIONS D INSTALLATION Illustration 1 Si vous rencontrez de tels probl mes consultez un expert local en chemin e...

Page 14: ...vantde passage pour le connecteur mural de la chemin e en t le d acier de calibre 24 minimum d paisseur avec un espace d air de deux pouces 2 minimum entre la paroi ext rieure de la section de la chem...

Page 15: ...murale d au moins douze pouces 12 au dessus de la cartouche murale i la valeur R est donn e pas de conversion requise ii le facteur k est donn avec une paisseur T requise en pouces R 1 k xT iii le fa...

Page 16: ...c un rev tement en acier inoxydable peut tre requis 12 Il est recommand que pas plus de deux coudes de 90 soient utilis s dans l installation du conduit Plus de deux coudes de 90 pourraient diminuer l...

Page 17: ...u soit bien tabli environ 20 minutes faites attention la surchauffe 8 R ajustez l arriv e d air jusqu la vitesse de combustion d sir e Si un exc s de fum e remplit le foyer ouvrez l g rement l arriv e...

Page 18: ...aporteetlaissezlecimentprendrependant trois quatre heures avant de rallumer un feu Assemblage de la Porte AMESTI R 450 POIGNEE FROIDE ET CONTROLE D ARRIVEE D AIR Le fabricant inclut une poign e d acie...

Page 19: ...utiliser comme bois de chauffage Du bois sec et dur doit tre utilis Evitez les bois verts ou non s ch s Le bois vert en plus de ne bruler qu 60 de la valeur nerg tique des bois secs d posera de la cr...

Page 20: ...PROPRIETAIRE ORIGINAL AMESTI garantit que toutes les pi ces de ce po le se r f rant des mat riaux et de fabrication seront exemptes de d fauts au moment de l achat Le fabricant tend les garanties suiv...

Page 21: ...reporter l autocollant sur l int rieur des pieds du foyer pour compl ter cette partie Num ro de mod le_________________________ Date d achat _____________________________ Prix d achat ________________...

Page 22: ......

Reviews: