18-BH15D7-5

©  2006 American Standard Inc. All rights reserved

Model:

TAYPLUS103A

INSTALLER'S
GUIDE

ALL phases of this installation must comply with
NATIONAL, STATE AND LOCAL CODES.

Hybrid Comfort™ System

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service information pack upon completion of work.

Library
Product Section
Product
Model
Literature Type
Sequence
Date
File No.
Supersedes

INSTALLATION OF BONNET THERMOSTAT THT01248

(BAYSEN03ATEMPAA) ON ALL OIL FURNACES

"A" COIL APPLICATION (UPFLOW)

1.  Remove the front cover panel from the "A" coil enclosure.
2.  Select a location to make a 1-1/2" hole for the bonnet

thermostat to pass through (see figure 2) in front of the coil

baffle of "A" coil.

3.  The location of the 1-1/2" hole should be on a vertical line

(plane) to the top of the "A" coil and approximately 4"- 6"

down from the front end of the coil.

4. With the template provided make the 1-1/2" hole in the coil

baffle and install the bonnet thermostat with the screws

provided in the kit.

5. Drill a 3/8" hole in the front cover panel for field wiring and

install the grommet provided with this kit.

6.  Connect the bonnet thermostat leads in the Plus One Control

Center through the grommet. (See hookup diagram).

7.  Replace the front cover panel on "A" coil enclosure and

secure.

"A" COIL APPLICATION (DOWNFLOW)

1.  Select a location on the air entering side of the coil enclosure

to make a 1-1/2" hole for the bonnet thermostat to pass

through (see Figure 1, page 2).

2.  The location of the 1-1/2" hole should be on a horizontal line

(plane) to the top of the "A" coil. The bonnet thermostat

cannot be in contact (touching) the coil.

3. With the template provided, make the 1-1/2" hole in the coil

enclosure and install the bonnet thermostat with the screws

provided .

GENERAL

The Plus One system was designed to combine warm air furnaces

(indoor units) with heat pumps for maximum comfort and energy

efficiency during the entire year.
This is compatible only with furnaces having 24V transformers at

least 35 VA.
The control center enclosure is made of galvanized steel, with an

attractive decorative logo on the front panel.
This enclosure is 9-3/16" x 7-1/8" x 2-1/2" in size.  When the

cover is removed, the components are readily accessible for field

hook-up or service.  All field electrical connections are to

terminal board, or wire nuts (field supplied). This assembly can

be mounted in any position.

INSPECTION

1.  Unpack the Plus One Control Center and  remove cover.

Included inside are:

Control Box Assembly

Installer's Guide

2.  Check for any shipping damage. If there is any, report it to the

carrier immediately.

3.  The field electrical connections and wiring must be done in

accordance with the "National Electrical Code" and must

comply with local electrical codes.

4.  Minimum gauge 18 AWG thermostat

 

wire.

SYSTEM USAGE AND INSTALLATION

This system uses a heat pump outdoor section with an  indoor

heat pump coil, a Plus One Control Center and a warm air

furnace.
The Plus One Control Center as shipped from the factory is for

operation in the "non-restricted" mode.  For "restricted" opera-

tion, field wire in accordance with appropriate diagram (included

in these instructions).  TAYSTAT250A is required.
1.  The indoor coil must be installed on the supply side of the

furnace.

2.  The Plus One Control Center is installed in close proximity to

the furnace.

3.  The outdoor thermostat (when used in restricted operation

only) is installed in the outdoor section in accordance with

TAYSTAT250A installation requirements.

NOTE: For Load Shedding in the heating cycle, use the restricted

hook up diagram. The utility company's load shedding relay will

be wired in place of the ODT as shown. The utility company's relay

must be a SPDT switch type.

NOTE: Do not connect wires to the W terminal at the comfort

control terminal #1 at ODT if utility company requires lockout

(restriction) of gas furnace at an outdoor temperature above

the setting on the ODT. Emergency heat cycle and furnace

blower will come on if the comfort control is in Emergency

Heat mode.

Summary of Contents for Hybrid Comfort TAYPLUS103A

Page 1: ...iciency during the entire year This is compatible only with furnaces having 24V transformers at least 35 VA The control center enclosure is made of galvanized steel with an attractive decorative logo on the front panel This enclosure is 9 3 16 x 7 1 8 x 2 1 2 in size When the cover is removed the components are readily accessible for field hook up or service All field electrical connections are to...

Page 2: ...o the Emergency Heat Mode converts the system to furnace only operation A COIL HORIZONTAL APPLICATION FRONT COIL BAFFLE A COIL BONNET THERMOSTAT COIL ENCLOSURE SUPPLY DUCT A COIL UPFLOW APPLICATION SUPPLY DUCT A COIL DOWNFLOW APPLICATION NOTE 3 3 NOTE 2 2 FLAT COIL HORIZONTAL APPLICATION NOTE 1 CLASS 2 LOW VOLTAGE WIRING TO SYSTEM CONTROLLER SEE NOTE 1 ABOVE HORIZONTAL FURNACE from 146682 FLAT COI...

Page 3: ...INSTALLER S GUIDE 3 SINGLE STAGE HEAT PUMP NON VARIABLE SPEED GAS FURNACE UN RESTRICTED MODE OF OPERATION SINGLE STAGE HEAT PUMP NON VARIABLE SPEED GAS FURNACE RESTRICTED MODE OF OPERATION ...

Page 4: ...INSTALLER S GUIDE 4 TWO STAGE HEAT PUMP VARIABLE SPEED GAS FURNACE UN RESTRICTED MODE OF OPERATION TWO STAGE HEAT PUMP VARIABLE SPEED GAS FURNACE RESTRICTED MODE OF OPERATION ...

Page 5: ...INSTALLER S GUIDE 5 TWO STEP HEAT PUMP VARIABLE SPEED GAS FURNACE UN RESTRICTED MODE OF OPERATION TWO STEP HEAT PUMP VARIABLE SPEED GAS FURNACE RESTRICTED MODE OF OPERATION ...

Page 6: ...INSTALLER S GUIDE 6 SINGLE STAGE HEAT PUMP SINGLE STAGE OIL FURNACE UN RESTRICTED MODE OF OPERATION SINGLE STAGE HEAT PUMP SINGLE STAGE OIL FURNACE RESTRICTED MODE OF OPERATION ...

Page 7: ...INSTALLER S GUIDE 7 TWO STAGE HEAT PUMP VARIABLE SPEED OIL FURNACE UN RESTRICTED MODE OF OPERATION TWO STAGE HEAT PUMP VARIABLE SPEED OIL FURNACE RESTRICTED MODE OF OPERATION ...

Page 8: ...PERATION TWO STEP HEAT PUMP VARIABLE SPEED OILFURNACE RESTRICTED MODE OF OPERATION Trane A business of American Standard Companies Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specifications without notice ...

Reviews: