Model:

BAYECON101A
BAYECON102A
BAYRLAY004A

(Relay required in WC* Units)

Down Discharge Economizer and Rain Hood

Used with:

2/4TC*,WC*,YC*,DC* *018-036A
2/4TC*,WC*,YC*, DC* *042-060A

Inspect Contents

You must report damage and make claims to the transporta-
tion company immediately. Report missing parts to your sup-
plier immediately and replace with authorized parts only.

3.  Install Economizer Assembly

Note:

 You must first install the filter rack per the instruc-

tions provided and then install the economizer.

2.  Swing the return air damper section down so that it rests

on the bottom of the unit. The economizer will sit
completely over the return air opening in the bottom of
the unit.  See Figures 5 on page 4. Screw the economizer
assembly together with one assembly screw in the side of
the economizer. Tighten the linkage rod between the
return air dampers.

3. Insert 2 screws through the holes in the front face of the

unit and into the matching attachment holes in the econo
mizer assembly. See Figure 6 on page 4.

4.

Insert a screw through the pre-punched hole in the side
flange of the return air damper and into the mating hole
in the economizer assembly and tighten. See Figure 5 on
page 4.

18-HE39D8-7

Identify Economizer Kit Contents

Refer to Figures 1 and 2 on page 2 to identify the kit
contents.

Install Economizer Kit

General

The economizer is a multi-damper design. It is installed in  the
return air stream and is connected to the unit low voltage sup-
ply through wire leads. The economizer is fully accessible
through the Coil access panel.

Important: 

The Economizer installation requires that you first

install an air filter rack ordered separately. Use:
BAYFLTR101A for 2/4YC*, WC*, TC*, DC* *018-3036A
BAYFLTR201A for 2/4YC*, WC*, TC*, DC* *042-3060A.

1.

 

Remove Power

      Disconnect and verify that power is off.

2. Remove Access Panels

Remove these four (4) access panels (see Figure 3, page 2):
• Control/Heat access panel
• Blower access panel
• Coil access panel
• Horizontal Return Air panel (discard or store)

When the economizer is installed in WC* models, relay
accessory kit BAYRLAY004A is required. Refer to the drawing
on page 9 to make your relay wiring connections in the Control
Box.

Installer’s Guide

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with this unit.  Please return to service

information pack upon completion of work.

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

WARNING:

ELECTRIC SHOCK HAZARD
OPEN AND LOCK OUT ALL UNIT DISCONNECTS PRIOR TO
ACCESSORY INSTALLATION OR UNIT MAINTENANCE, TO
PREVENT INJURY OR DEATH FROM ELECTRICAL SHOCK OR
CONTACT WITH MOVING PARTS.

SAFETY HAZARD
DO NOT REMOVE END COVERS FROM ECONOMIZER AC-
TUATOR; THE SPRING-RETURN ASSEMBLY MAY RELEASE
AND CAUSE PERSONAL INJURY.

WARNING

!

!

WARNING

Use care when inserting the economizer in the return air com-
partment, to prevent damaging the foil faced insulation.

CAUTION

!

1. The economizer ships with the return air damper folded

up to allow the assembly to fit through the Coil opening
in the side of the unit, see Figures 1 and 2 on page 2.

Insert the economizer assembly into the unit through the
Coil access panel opening. See Figure 4 on page 3.

Summary of Contents for BAYECON101A

Page 1: ...cessible through the Coil access panel Important The Economizer installation requires that you first install an air filter rack ordered separately Use BAYFLTR101A for 2 4YC WC TC DC 018 3036A BAYFLTR2...

Page 2: ...TC WC or YC Unit Horizontal Return Air Panel Down Flow Return Air Panel Blower Access Panel Control Box Access Panel Coil Access Panel Mixed Air Sensor Economizer Assembly Rainhood Assembly Mist Elimi...

Page 3: ...ptions at this time per instructions provided 6 Route Main Wiring 1 From the Economizer assembly pass the wire harness through the coil grommet See Figure 10 view A on page 7 Continue routing the harn...

Page 4: ...ert Assembly screw 1 Swing Down Return Air Damper Return Air Damper 3 Tighten Linkage rod Figure 6 Start Economizer s Front Mounting Screws Economizer outline Install two 2 screws into holes Leave ext...

Page 5: ...izer rain hood Figure 7 Mounting Rain Hood Top flange of hood slides under HVAC unit s top sealing flange HVAC unit s top sealing flange Hood HVAC unit 2 Drive six 6 self tapping screws into the keyho...

Page 6: ...0 2 82 View A Approximate Mounting Dimension See View A Return Duct Roofcurb Relief damper Mist eliminator filter Economizer rain hood Outside air dampers Return air dampers Required filter kit order...

Page 7: ...outing Behind Compressor Compartment and into Blower Compart ment 3 Pull the two 2 Mixed Air Sensor Wires with female quick connects from the Harness and Route Down Near the Mixed Air Sensor Connect t...

Page 8: ...PAGE 8 INSTALLER S GUIDE Figure 11 TC YC Economizer Connection Diagram...

Page 9: ...PAGE 9 INSTALLER S GUIDE Figure 12 WC Economizer Connection Diagram...

Page 10: ...set screws This motor checkout ensures that 1 The motor operates the load 2 The motor responds properly to the controller 3 There is no binding of the linkage or motor stalling at any point of travel...

Page 11: ...s Sr and Led turns on motor drives toward open C 1 To simulate high and low enthalpy single enthalpy sensor reconnect factory installed 620 ohm resistor from termonals Sr and Connect 1 2K ohm 4074EJM...

Page 12: ...Inc 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement It reserves the right to change design and specification without notice 200...

Reviews: