![American Dynamics VM96 Installation Instructions Manual Download Page 5](http://html1.mh-extra.com/html/american-dynamics/vm96/vm96_installation-instructions-manual_2923648005.webp)
VIEW MANAGER 96 ENHANCED TOUCH TRACKER
8000-0748-02, REV. B1
INSTALLATION INSTRUCTIONS
5 of 6
The Touch Tracker may cycle several times
with an
r
in the upper right-hand section of the
LCD. An
A
indicates the address was accepted.
Press
Clear Entry
if the controller stalls with a
TTR
message at the bottom of the LCD screen
or if there is no text visible.
NOTE:
The Touch Tracker address defaults to
A1. If more than one Touch Tracker will be
used, you must change the address for all
Touch Trackers except the last one connected.
See step 3.
5. Set the Touch Tracker link address:
a. Press
0
, then
Menu
to start the Utility Menu
on the Touch Tracker you just connected.
b. Press
2
to set the link address.
c. Enter an address (2-8) for the Touch
Tracker. The Touch Tracker checks for
address availability. If the address is
accepted, the message
Address
Granted
,
Press Clear
appears on the
LCD.
d. Press
Clear Entry
twice to exit the Utility
Menu.
6. Disconnect the Touch Tracker, and repeat
steps 3-5 for each Touch Tracker (except the
last one). When addresses have been
assigned to the Touch Trackers, reconnect all
Touch Trackers.
The VM96 system is ready to use.
Remote Touch Tracker
Overview
VM96 supports communication with a remotely
located Touch Tracker using RS-232
communications. A remote Touch Tracker should
be used when the Touch Tracker will be located
more than 1000m (3300 feet) from the host. Short
haul modems allow the distance to be extended
and support communications over voice-grade
leased or switched lines.
When installing a remote Touch Tracker, keep the
following requirements in mind:
•
The short haul modems must support 1200,
2400, 4800 or 9600 baud. Use the instructions
included with the modems for installation and
configuration. These are the only baud rates
supported by the Touch Trackers.
•
The Touch Trackers must be configured to the
same baud settings as the short haul modems.
•
A local Touch Tracker must be dedicated while
the remote unit is in use. The two Touch
Trackers connect through the RS-232 ports on
their respective EIMs.
•
The RS-232 cable cannot exceed 15m (50 ft).
Use low capacitance, 100% shielded EIA
RS-232 cabling.
•
Both Touch Trackers must be the same type
(Enhanced Touch Trackers) and have the
same firmware version.
The following illustrates a remote Touch Tracker
installation:
T
T
T
The following chart provides the wiring information
between the two EIMs.
Wire
Local and Remote EIM
1
Pin 2-Tx
2
Pin 3-Rx
3
Pin 5 Ground
Note
: When attaching with a modem, use a
conventional modem cable and DB-25 to DB-9
converter, if required.
Local
Modem
Remote
Modem
Dedicated Local
Touch Tracker
and EIM
Remote
Touch Tracker
and EIM
SensorNet
RS-232
RS-232