American Dynamics VM96 Installation Instructions Manual Download Page 5

VIEW MANAGER 96 ENHANCED TOUCH TRACKER  

8000-0748-02, REV. B1 

INSTALLATION INSTRUCTIONS

 

5 of 6 

 

 

The Touch Tracker may cycle several times 
with an 

r

 in the upper right-hand section of the 

LCD. An 

A

 indicates the address was accepted. 

 Press 

Clear Entry

 if the controller stalls with a 

TTR

 message at the bottom of the LCD screen 

or if there is no text visible.  

 

NOTE:

 The Touch Tracker address defaults to 

A1. If more than one Touch Tracker will be 
used, you must change the address for all 
Touch Trackers except the last one connected. 
See step 3. 

5.  Set the Touch Tracker link address: 

a. Press 

0

, then 

Menu

 to start the Utility Menu 

on the Touch Tracker you just connected. 

b. Press 

2

 to set the link address. 

c.  Enter an address (2-8) for the Touch 

Tracker. The Touch Tracker checks for 
address availability. If the address is 
accepted, the message 

Address 

Granted

Press Clear

 appears on the 

LCD. 

d. Press 

Clear Entry

 twice to exit the Utility 

Menu.  

6.  Disconnect the Touch Tracker, and repeat 

steps 3-5 for each Touch Tracker (except the 
last one). When addresses have been 
assigned to the Touch Trackers, reconnect all 
Touch Trackers.  

The VM96 system is ready to use. 

 
 

Remote Touch Tracker 
Overview 

VM96 supports communication with a remotely 
located Touch Tracker using RS-232 
communications. A remote Touch Tracker should 
be used when the Touch Tracker will be located 
more than 1000m (3300 feet) from the host. Short 
haul modems allow the distance to be extended 
and support communications over voice-grade 
leased or switched lines.  
When installing a remote Touch Tracker, keep the 
following requirements in mind: 

  The short haul modems must support 1200, 

2400, 4800 or 9600 baud. Use the instructions 
included with the modems for installation and 
configuration. These are the only baud rates 
supported by the Touch Trackers. 

  The Touch Trackers must be configured to the 

same baud settings as the short haul modems. 

  A local Touch Tracker must be dedicated while 

the remote unit is in use. The two Touch 
Trackers connect through the RS-232 ports on 
their respective EIMs. 

  The RS-232 cable cannot exceed 15m (50 ft). 

Use low capacitance, 100% shielded EIA  
RS-232 cabling. 

  Both Touch Trackers must be the same type 

(Enhanced Touch Trackers) and have the 
same firmware version. 

The following illustrates a remote Touch Tracker 
installation:  

T

T

T

 

The following chart provides the wiring information 
between the two EIMs. 

Wire 

Local and Remote EIM 

Pin 2-Tx  

Pin 3-Rx  

Pin 5 Ground 

 

Note

: When attaching with a modem, use a 

conventional modem cable and DB-25 to DB-9 
converter, if required. 

Local 

Modem

Remote

Modem

Dedicated Local 

Touch Tracker 

and EIM 

Remote  

Touch Tracker 

and EIM

SensorNet

RS-232

RS-232

Reviews: