39
12) Flame (Burner Control Failure) input L.E.D. indicator
13) Power Supply
e. Open main door. The dryer
must stop
and
ALL
indicator dots of the microprocessor (computer) L.E.D.
(light emitting diode) display
must go out
. (Refer to
illustration
on
page 37
.)
f. Try to restart the dryer with the main door open.
g. The microprocessor (computer) boards L.E.D. display
must read
MAIN
dOOR
.
h. Close the main door and restart the dryer.
i. Functional check of microprocessor (computer) board is complete.
2. Hot Surface Ignition (HSI) System
a. Upon completing installation of the
replacement Hot Surface Ignition
(HSI) module, reestablish power to
the dryer.
b. The HSI modules red indicator
light will light for up to approximately
5-seconds (self check routine).
If the HSI modules red indicator
light stays on or flashes continuously,
then the HSI module is wired
incorrectly or has failed.
c. Start the drying cycle.
d. The hot surface ignitor will turn on, and a few seconds later the gas valve
will
be
energized. After
approximately 4-seconds the hot surface ignitor will shut off.
Ignition (flame) should now be established.
e. With the burner flame on, remove the flame sensor wire from the S2 terminal of the HSI module.
The
burner flame must shut off immediately.
f. Stop the drying cycle, with the flame sensor wire still removed, restart the drying cycle.
g. The hot surface ignitor will turn on, and after a few seconds later the gas valve
will
be
energized and the
hot surface ignitor will shut off. Ignition (flame)
should be
evident for approximately 7-seconds and
then shut off.
h. The HSI module will attempt two (2) additional ignition trials after which the HSI module will lockout and
the red indicator light
will flash continuously.
i. Functional check of the Hot Surface Ignition (HSI) Module is complete.
1) Replace the flame sensor wire from the S2 terminal to the HSI module.