SMD23E2 and SMD24E2 User Manual
C
OMMAND
M
ODE
D
ATA
F
ORMAT
83
Programming Blocks
The following blocks are used to program an Assembled Move. Both of the move types, Blend Move, and
Dwell Move, are programmed exactly the same way. The bit configuration used when starting the move
determines which type of Assembled Move is run.
First Block
Table R6.18 Assembled Move First Programming Block
Unused words are ignored by the SMD23E2 and SMD24E2 and can be any value, including parameter values
from the previous command.
Once the first block is transmitted, the SMD23E2 or SMD24E2 responds by setting bits 8 and 9 in Status Word 0.
(See
starting on page 84.) Once these are set, you can then start transmitting Segment
Blocks.
Segment Block
Table R6.19 Assembled Move Segment Programming Block
Note that each Segment Block starts with bits 11 and 12 in Command Word 0 set to “1” (16#1800). When the
unit sees bit 12 of Command Word 0 set, it will accept the block and reset bit 9 in Status Word 0. When your pro-
gram sees this bit reset, it must respond by resetting bit 12 of Command Word 0. The SMD23E2 or SMD24E2
will respond to this by setting bit 9 in Status Word 0 and the next Segment Block can be written to the unit. You
can write a maximum of sixteen Segment Blocks for each Assembled Move.
PROFINET
Word
Function
Units
Range
0
16#0800
1
See pg. 73
2
Unused
See Note Below
3
Unused
See Note Below
4
Unused
See Note Below
5
Unused
See Note Below
6
Unused
See Note Below
7
Unused
See Note Below
8
Unused
See Note Below
9
Unused
See Note Below
PROFINET
Word
Function
Units
Range
0
16#1800
1
See pg. 73
2
Rel. Target Position: Upper Word
Steps
Combined value between
–8,388,608 and +8,388,607
3
Rel. Target Position: Lower Word
4
Programmed Speed: Upper Word
Steps/Second
Combined value between
the Configured Starting
Speed and 2,999,999
5
Programmed Speed: Lower Word
6
Acceleration
Steps/sec/ms
1 to 5000
7
Deceleration
Steps/sec/ms
1 to 5000
8
Reserved
Must equal zero for compat-
ibility with future releases.
9
Acceleration Jerk
0 to 5000
Summary of Contents for SMD23E2 Series
Page 10: ...ABOUT THIS MANUAL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Page 44: ...MOTION CONTROL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Page 54: ...CALCULATING MOVE PROFILES SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Page 88: ...COMMAND MODE DATA FORMAT SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Page 128: ...MODBUS TCP CONFIGURATION SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 128 Notes...
Page 134: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...