C
ONFIGURATION
M
ODE
D
ATA
F
ORMAT
SMD23E2 and SMD24E2 User Manual
ADVANCED MICRO CONTROLS INC.
66
Output Data Format (continued)
Configuration Word 1 Format (continued)
Bit 1:
IN2_Active_Level –
Determines the active state of Input 2. Set to “0” if your sensor has Normally
Closed (NC) contacts and the input is active when there is no current flow through it. Set to “1” if
your sensor has Normally Open (NO) contacts and current flows through the input when it is active.
Bit 0:
IN1_Active_Level –
Determines the active state of Input 1. Set to “0” if your sensor has Normally
Closed (NC) contacts and the input is active when there is no current flow through it. Set to “1” if
your sensor has Normally Open (NO) contacts and current flows through the input when it is active.
If you are not using the input, sets its Active_Level bit to “1”. The input will always report as
inactive in the network data.
Notes on Other Configuration Words
Information on the
Configuration Mode Data Format
used when programming the Starting Speed can
be found on page 61.
Changes to the Idle Current only take effect at the
end of the first move after re-configuration
.
Input Data Format
The format for the Network Input Data when an SMD23E2 or SMD24E2 is in Configuration Mode is shown
below.
Table R5.5 Network Input Data Format: Configuration Mode
Configuration Word 0 Format (Word 0)
When the Configuration data is valid and accepted, this word mirrors the value of the Configuration Word 0
written to the SMD23E2 or SMD24E2. When the data written to it is invalid, the unit remains in Command
Mode and sets the Configuration Error bit in the first word written back to the host controller. The format of
this word is explained in the
section starting on page 84.
Starting Speed Format
The Starting Speed parameter is always programmed using the
Configuration Mode Data Format
described on page 61.
PROFINET
Word
Configuration Data
0
Mirror of Output Configuration Word 0
1
Mirror of Output Configuration Word 1
2
Mirror of Starting Speed: Upper Word
3
Mirror of Starting Speed: Lower Word
4
Mirror of Motor Steps/Turn
5
0000
6
Mirror of Encoder_Resolution
7
Mirror of Idle Current Percentage
8
Mirror of Motor Current (X10)
9
0000 or
Status message when writing
Configuration data to flash memory.
Summary of Contents for SMD23E2 Series
Page 10: ...ABOUT THIS MANUAL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Page 44: ...MOTION CONTROL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Page 54: ...CALCULATING MOVE PROFILES SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Page 88: ...COMMAND MODE DATA FORMAT SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Page 128: ...MODBUS TCP CONFIGURATION SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 128 Notes...
Page 134: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...