background image

ADVANCED MICRO CONTROLS INC.

10

POWER CONNECTOR AND INDICATOR LED’s

Power Connector

The SD17040C operates on 115Vac.  If 230Vac is the only power available, consider using one 
of the 230Vac drivers available from AMCI.  Information on these drivers can be found on our 
website, http://www.amci.com.  If this is not an option, a step-down transformer must be 
installed to power the SD17040C.  The transformer must have a minimum power rating of 600 
VA.

The SD17040C must be grounded for proper operation.  Grounding is accomplished with the 
GND pin on the power connector, and through proper bonding to the enclosure.  Power con-
nections should be tight.  Loose connections may lead to arcing which will heat the connector.  
Phoenix Contact specifies a tightening torque of 4.4 to 5.4 lb-in (0.5 to 0.6 nM) 

Indicator LED’s

The SD17040C has two indicator LED’s.

STEP/FAULT  

!

!

Green:  

Driver Operational

!

Flashing Green:

  Driver Operational, Receiving Pulses

!

Red:

  Driver Fault 

(The Over Temperature and Over Current faults can be cleared with the Disable Input.)

1) Over Temperature Fault:  The heatsink temperature exceeds 90°C (195°F)

2) Over Current Fault:  Generally, a short exists somewhere in the system.  This can be a short in the 

motor or in the driver itself.

A) Phase–Phase Short: There is an electrical short between the two motor windings.  The short 

exists in the motor cable or in the motor itself.

B) Phase–Ground Short: One of the motor’s windings is shorted to earth ground.  (The EARTH 

GND terminal of the Motor Connector is used as the reference point.)  The 
fault can be in the motor cable or in the motor itself.

C) Back EMF: In applications with large motors and high deceleration rates, back-EMF generated 

by the motor may also cause this fault.

3) Interlock Fault:  The two Interlock Terminals on the motor connector are not connected with a short 

jumper.

!

Flashing Red:

  Current Loop Gain AUTOID Error.  

There is a problem with the motor wiring or the motor 

current is set to zero.

!

Flashing Red/Green @ 1Hz:

  Step Violation:  

The indexer sent step pulses to the SD17040C before the 

driver was ready for them.  The driver was disabled, in a fault condition, or had not completed its initialization 

sequence on power up or reset.  The stepper motor position will be invalid.  The motor is not disabled and can still 

be driven.  While there is motion, the LED will flash at approximately 4 Hz.

!

CURRENT LOOP GAIN:

  This LED is also used when the Current Loop Gain is set to AutoID.  (SB2:1-

5 all turned off)  When set to AutoID, the driver will determine the parameters of the attached motor and 
will flash the Step/Fault LED green the number of times that the parameter should be set to.  Flashing 
red indicates a problem with the motor wiring or the motor current is set to zero.  Further information 
can be found in the next section of the manual, Verifying System Setup. 

Power  

!

!

Green:  

Power is applied to the driver in the range of 95 or 132 Vac.

AC POWER

95 – 132 V

AC

50/60 Hz

GND

N

L

Summary of Contents for SD17040C

Page 1: ...s e r M anual Manual 940 0S110 Table of Contents General Information 2 Introducing the SD17040C 3 Specifications 4 Mounting the SD17040C 5 Switch Settings 6 Connecting Your Controller 7 Connecting You...

Page 2: ...at its option repair or replace free of charge any equipment covered by this warranty which is returned shipping charges prepaid within eighteen months from date of invoice and which upon examination...

Page 3: ...uitry Back EMF Protection Circuity Programmable Step Resolution from 200 to 50 800 steps per turn Programmable Idle Current Reduction Programmable Current Loop Gain Programmable Pulse Train Input Step...

Page 4: ...Motor Current Switch selectable from 1 0 to 4 0ARMS in 0 1 Amp steps Idle Current Reduction Switch selectable to Not reduced To 69 To 50 or To 0 Motor current is reduced to selected level if a step p...

Page 5: ...so take steps to ensure that the two are electrically bonded together If necessary remove paint for the bolt mounting surfaces of the panel to ensure adequate electrical bonding Airflow and Wiring Spa...

Page 6: ...0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 1 1 0 0 0 0 0 0 1 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 0...

Page 7: ...lses The active state of the Disable Input is set by switch SB1 4 RLD An additional load resistor may be required on some PLC outputs to improve switching time A symptom of this problem is that the mo...

Page 8: ...e and is not ready to accept pulses Both ends of the output are uncommitted so it can be wired as a sourcing or sinking output The figure shows a typical connection as a sourcing output RLIMIT A resis...

Page 9: ...TAP B B EARTH GND A CTAP INTERLOCK A A 8 LEAD MOTOR Eight Lead Series Connected Motor Case INTERLOCK B CTAP B B EARTH GND A CTAP INTERLOCK A A 8 LEAD MOTOR Eight Lead Parallel Connected Motor Case INT...

Page 10: ...r itself B Phase Ground Short One of the motor s windings is shorted to earth ground The EARTH GND terminal of the Motor Connector is used as the reference point The fault can be in the motor cable or...

Page 11: ...for your system Turn off all of the switches in switch bank 2 and then verify that the motor current is set correctly and the motor is attached to the driver Cycle power to the driver The STEP FAULT...

Page 12: ...ne turn While the turn is in progress the STEP LED should blink Verify that the motor rotated in the correct direction for one complete turn If you are using an optical encoder or other position feedb...

Page 13: ...be active The active state power applied or power removed is set by DIP switch SB1 4 This switch may be set incorrectly 2 The Idle Current Reduction may be set to its To 0 setting With this setting cu...

Page 14: ...he driver is config ured for the Step Direction format the motor will rotate counter clock wise when the driver receives CW pulses and it will not rotate at all when the driver receives CCW pulses If...

Page 15: ......

Page 16: ...VANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ADVANCED MICRO CONTROLS INC ADVANCED MICRO CONTROLS INC ADVANCED MICRO CONTROLS INC 20 GEAR DRIVE TERRYVILLE CT 06786 T 860 585 1254 F 860 584 1973...

Reviews: