Status LED’s
Module Status (MS) LED
The Module Status LED is a bi-color red/green LED. The state of the LED depends on the state of the net-
work adapter module.
Table R1.1 Module Status LED States
Network Status (NS) LED
The Network Status LED is a bi-color red/green LED. The state of the LED depends on the protocol the
NXEE2 is configured to for.
Table R1.2 Network Status LED States
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power
Alternating
Red/Green
Power up Self-Test (Occurs very quickly on power up.)
Flashing
Green
Waiting for valid physical connection to the network.
Not Implemented
Steady Green
Drive and Network are operational.
Device Name or IP Address
are set.
Flashing Red
Initializing: IP Address Conflict
Initializing: Device Name or
IP Address are not set.
If the Network Status LED is also flashing red, the IP Address or Network Protocol has
been changed. Cycle power to the unit to continue. If the Network Status LED is in any
other state, a write to flash memory has failed. Cycle power to the unit to clear this fault.
Steady Red
Major Fault. Cycle power to the unit to attempt to clear the fault.
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power
No power or no TCP
connections
No power, duplicate IP
address, mismatch in Device
Name, or no connection to the
IO Controller.
Alternating
Red/Green
Power up Self-Test (Occurs very quickly when power is applied.)
Flashing
Green
Ethernet connection, but
no CIP connections
Indicates number of
connections with 2 second
delay between group. The
NXEE2 supports up to 5
concurrent connections.
On-line, Stop state.
A connection with the IO
Controller is established and
it is in its STOP state.
Steady Green
Valid Ethernet network
and CIP connections
Not Implemented
On-line, Run state.
A connection with the IO
Controller is established and
it is in its RUN state.
Blinking Red
If the MS LED is steady
green: Network
Connection Timeout
Not Implemented
Not Implemented
If the MS LED is blinking red: IP Address or Network Protocol changed: Cycle power
Steady Red
Duplicate IP address on network.
Not Implemented.
Summary of Contents for NXEE2
Page 22: ...DATA FORMATS NXEE2 User Manual ADVANCED MICRO CONTROLS INC 22 Notes ...
Page 32: ...INSTALLING THE NXEE2 NXEE2 User Manual ADVANCED MICRO CONTROLS INC 32 Notes ...
Page 40: ...SET THE IP ADDRESS AND PROTOCOL NXEE2 User Manual ADVANCED MICRO CONTROLS INC 40 Notes ...
Page 42: ...PROTOCOL SPECIFIC INFORMATION NXEE2 User Manual ADVANCED MICRO CONTROLS INC 42 Notes ...
Page 54: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 54 Notes ...
Page 60: ...ETHERNET IP EXPLICIT MESSAGING EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 60 Notes ...
Page 64: ...MODBUS TCP CONFIGURATION Modbus TCP Protocol ADVANCED MICRO CONTROLS INC 64 Notes ...
Page 72: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...
Page 74: ...PROFINET NETWORK CONFIGURATION PROFINET Protocol ADVANCED MICRO CONTROLS INC 74 ...