background image

Figure 10 Damper settings

5 Commissioning

Inspect installation and ensure it has been
carried out in accordance with these
instructions. 

Ensure that electrical and gas supplies are
isolated.

The gas supply should be purged and 
tested for soundness in accordance with the
British Standard BS 6891:1998, 
BS 7671:1992, IGE/UP/2 and any other
British Standards and Codes of Practice.

Ensure that the settings of any time switch
and thermostat are such that the heating
system will be required to operate (or put 
the mode switch to ‘constant’).

Before attempting to start up the heating
system it is essential to perform the
preliminary balancing of the vacuum level at
each burner unit.

Isolate each heater unit by unplugging each
electrical connector and closing each gas
isolating valve.

Heater type

Damper setting when hot (mbar)

Heater type

Damper setting when hot (mbar)

AR

13

SHN/

22

1.7

ARE

13

SHN/

22

1.1

AR

13

SHP/

22

1.7

ARE

13

SHP/

22

1.1

AR

22

SHN/

27

1.4

ARE

22

SHN/

27

1.1

AR

22

SHP/

27

1.4

ARE

22

SHP/

27

1.1

AR

22

SHN/

32

1.4

ARE

22

SHN/

32

1.1

AR

22

SHP/

32

1.4

ARE

22

SHP/

32

1.1

AR

22

SHN/

36

1.4

ARE

22

SHN/

36

1.1

AR

22

SHP/

36 

1.4

ARE

22

SHP/

36

1.1

AR

22

SHN/

39

1.4

ARE

22

SHN/

39

1.1

AR

22

SHP/

39

1.4

ARE

22

SHP/

39

1.1

AR

35

SHN/

33

1.5

ARE

35

SHN/

33

1.2

AR

35

SHP/

33

1.5

ARE

35

SHP/

33

1.2

AR

35

SHN/

42

1.2

ARE

35

SHN/

42

1.0

AR

35

SHP/

42

1.7

ARE

35

SHP/

42

1.0

AR

35

SHN/

51

1.0

ARE

35

SHN/

51

1.0

AR

35

SHP/

51

1.5

ARE

35

SHP/

51

1.0

AR

40

SHN/

42

1.6

ARE

40

SHN/

42

1.4

AR

40

SHP/

42

1.4

ARE

40

SHP/

42

1.4

AR

45

SHN/

50

1.9

ARE

45

SHN/

50

1.6

AR

45

SHP/

50

2.0

ARE

45

SHP/

50

1.6

AR

45

SHN/

60

2.0

ARE

45

SHN

/60

1.9

AR

45

SHP/

60

2.3

ARE

45

SHP/

60

1.6

AR

50

SHN/

50

1.9

ARE

50

SHN/

50

1.8

AR

50

SHP/

50

2.0

ARE50SHP/50

2.3

AR

50

SHN/

60

2.0

ARE

50

SHN/

60

1.8

AR

50

SHP/

60

2.3

ARE50SHP/60

2.3

N & P refer to natural gas or propane respectively.

Adjust the damper at exit of each heater
using a 4mm hexagon wrench in the M8
locking screw. Observing the vacuum
reading using a ‘U’ tube manometer
connected to the vacuum test point (see
figure 4) set each damper in turn to give a
hot conditions reading as below.

Referring to each unit

Open isolating valve and test gas
connections for soundness using leak
detecting solution. Remove the combustion
chamber cover plate by unscrewing the
fixing screws. Take care not to damage the
sealing gasket. Inspect the burner and
electrode assemblies ensuring these are
securely fixed and all electrical connections
securely made. Replace the cover plate
ensuring that the sealing gasket is correctly
positioned and the screws are fully
tightened. The heater will not operate until
this plate is refitted.

Remove the safety control housing cover
plate by unscrewing the securing screws
and folding down/lifting off the plate.

Ensure all internal components are securely
fixed and all connections securely made.

Reinsert the electrical connector to the
burner control assembly.

To allow the heater to start up it is
necessary to switch off the whole system 
at the time switch or manual switch and
allow the fan to stop completely before 
switching on again. At this point the
individual heater unit will start up with 
the following sequence.

The red 

mains on

lamp will illuminate and

the main fan will start to run. Safe-start
checks are carried out automatically. After
the fan has run up to full speed and a
satisfactory vacuum condition has been
established at the burner, a purge period of
approximately 9 seconds will commence.

At the end of the purge period the ignition
sequence will commence. The spark ignition
will be energised producing a spark at the
ignition electrode. The gas solenoid valve 
is energised and will open.

9

Summary of Contents for Herringbone HB

Page 1: ...HERRINGBONE HB COMBINED FLUE SYSTEM...

Page 2: ...Index General arrangement of Ambi Rad Herringbone system Instructions and installation Manifold assembly Fan to flue arrangement Commissioning Control system Service instructions 7 6 5 4 3 2 1 1...

Page 3: ...arrangement The exhaust flue should be adequately supported from the building structure and installed in accordance with the British Standard Code of Practice Flues for Gas Appliances Local and Minis...

Page 4: ...ters in the desired position the manifold system should be laid out on the floor where possible to the design layout before erecting After allowing for a minimum of 75mm 3in of penetration of the fitt...

Page 5: ...Figure 2 Figure 3 Figure 4 Important fit damper in vertical position Gas flow Important fit rivets and jointing compound SEAL ALL JOINTS 4...

Page 6: ...AR installation manual GB ARE E 079 0501 Figure 5 3 4 Condensate trap A condensate trap assembly must be provided at the end of the manifold system before the hot gas vacuum fan See figure 8a The min...

Page 7: ...o Combined Flue Heating System Do s and don ts of Herringbone systems The Type 0 and Type 2 vacuum fans have bottom horizontal discharge with rectangular connections flanged on the type 0 and must be...

Page 8: ...Figure 7 Vacuum fan mounting details Fan type 0 2 A 124 80 B 38 35 C 175 174 D 7 1 7 E 209 125 F 153 100 G 42 25 H 239 120 J 340 210 K 332 205 L 363 215 All dimensions are in millimetres see Fig 6 7...

Page 9: ...ure 8b Low fan arrangement Figure 8d Conventional flue arrangement roof exit Figure 8e Conventional flue arrangement wall exit Figure 8c Stainless steel telescopic through the wall arrangement availab...

Page 10: ...0 2 3 N P refer to natural gas or propane respectively Adjust the damper at exit of each heater using a 4mm hexagon wrench in the M8 locking screw Observing the vacuum reading using a U tube manometer...

Page 11: ...ssure or anti clockwise to decrease the pressure Set the burner pressure to the required figure given on the data label Switch off the heater by pulling out the mains connector Disconnect U tube manom...

Page 12: ...cordance with figure 12a or 12b and cut holes in the removable gland plate provided in the box Conduit or strain relief glands should be used Power onto panel Mode switch in off position Mode switch i...

Page 13: ...Figure 12a Single zone Herringbone control panel wiring diagram for Type 2 fan single phase incorporating the ARBB65 black bulb control thermostat 12...

Page 14: ...Figure 12b Wiring diagram for Type 0 fan single phase 13...

Page 15: ...r unit by undoing the four screws c Fix the base to the wall with two screws d Connect the sensor using a three core cable of not less than 0 5mm2 Maximum length of cable is 200m if 0 5mm2 is used Sec...

Page 16: ...4 489700 Facsimile 01384 489707 UK sales email sales ambirad co uk Website www ambirad co uk 7 Service instructions Under normal working conditions it is recommended that the Ambi Rad heater has a rou...

Reviews: