5
Configuration
Code
Configuration Feature
Option Code
Option
0
Off
1*
On only when ID fan runs
2
On when ID fan runs & room occupied
3
Runs continuously
4
On when room is occupied
E
Economizer
EP
Economizer with compressor assist
0
Off
1*
May be on anytime
2
Allowed on except in Off mode
3
Allowed on when indoor fan runs
4
Allowed on if room is occupied
5
Allowed on if room is not occupied
6
Allowed on when indoor humidity is high
0*
Door Switch
1
Motion Sensor
2
Front Desk
3
Wired Un-rented Set Back
4
Emergency Hydronic
5
Load Shedding
6
Alarm Sensor
0*
Door Switch
1
Motion Sensor
2
Front Desk
3
Wired Un-rented Set Back
4
Emergency Hydronic
5
Load Shedding
6
Alarm Sensor
0
Not used
15-80, 25*
% RH above which kit may run
0
Not used
15-60, 25*
% RH above which kit may run
0
No affect on indoor fan
1*
Indoor fan forced to run with Kit
uL
Config. Security Code
00* - 99
00* - 99
ub
Indoor Humidity Activation
un
Vent Dehumid Outdoor
Humidity Level
uu
Vent Dehumidification Kit
Fan Force
u9
Input Pins UN2 & COM
u8
Input Pins UN1 & COM
Smart Vent Operation
P0
Vent Dehumid Make-up Air
Kit Operation
P2
CONFIGURATION SETTINGS CHART (CONT.)