background image

15

CHECKING GAS PIPING

CAUTION

To prevent personal injury or property
damage due to fire, the following
instructions must be performed regarding
gas connections, pressure testing, location
of shutoff valve and installation of gas
piping.

Before placing in operation, leak test the unit and gas
connections. To avoid the possibility of explosion or fire,
never use a match or open flame to test for leaks. Never
exceed specified pressures for testing. Higher pressure
may damage the gas valve and cause overfiring, resulting
in heat exchanger failure.

This unit and shutoff valve must be disconnected from the
gas supply piping system before supply piping system
pressure testing with test pressures in excess of 1/2 psig
(3.48 kPa).

This unit must be isolated from the gas supply system by
closing its manual shutoff valve before pressure testing of
gas supply piping system with test pressures equal to or
less than 1/2 psig (3.48 kPa).

TANKS AND PIPING - PROPANE GAS UNITS

WARNING

To prevent death, personal injury or property
damage due to fire or explosion caused by
a propane gas leak,  install a gas detecting
warning device. Since rust can reduce the
level of odorant in propane gas, a gas
detecting warning device is the only reliable
way to detect a propane gas leak. Contact a
local propane gas supplier about installing
a gas detecting warning device.

WARNING

All metal inserts, screens or turbulators
must be removed from the heat exchanger
tubes when using propane gas. Failure to
comply could cause serious personal injury
or death. Failure to comply with this
requirement will also void warranty
coverage.

All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters (See
NBFU Manual 58).

For satisfactory operation, propane gas pressure must be
10 inch WC at the furnace manifold with all gas appliances
in operation. Maintaining proper gas pressure depends on
three main factors:

1. Vaporization rate, depending on temperature of the

liquid, and “wetted surface” area of the container or
containers.

2. Proper pressure regulation. (Two-stage regulation is

recommended for both cost and efficiency).

3. Pressure drop in lines between regulators, and be-

tween second stage regulator and the appliance. Pipe
size will depend on length of pipe run and total load of
all appliances.

Complete information regarding tank sizing for vaporiza-
tion, recommended regulator settings, and pipe sizing is
available from most regulator manufacturers and propane
gas suppliers.

Since propane gas will quickly dissolve white lead or most
standard commercial compounds, special pipe dope must
be used. Shellac base compounds resistant to the actions
of liquefied petroleum gases such as Gasolac, Stalactic,
Clyde’s or John Crane are satisfactory.

Refer to Figure 19 for typical propane gas installations.

Figure 19

Propane Gas Installation (Typ.)

PROPANE GAS PIPING CHARTS

Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. 
Capacities in 1,000 BTU/hour.

Pipe or

Nominal Pipe Size

Tubing

Tubing Size, O.D. Type L

Schedule 40

Length,

3/8"

1/2"

5/8"

3/4"

7/8"

1/2"

3/4"

Feet

10

730

1,700

3,200

5,300

8,300

3,200

7,500

20

500

1,100

2,200

3,700

5,800

2,200

4,200

30

400

920

2,000

2,900

4,700

1,800

4,000

40

370

850

1,700

2,700

4,100

1,600

3,700

50

330

770

1,500

2,400

3,700

1,500

3,400

60

300

700

1,300

2,200

3,300

1,300

3,100

80

260

610

1,200

1,900

2,900

1,200

2,600

100

220

540

1,000

1,700

2,600

1,000

2,300

125

200

490

900

1,400

2,300

900

2,100

150

190

430

830

1,300

2,100

830

1,900

175

170

400

780

1,200

1,900

770

1,700

200

160

380

730

1,100

1,800

720

1,500

To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879

Summary of Contents for GCI Series

Page 1: ...hem TheprecautionslistedinthisInstallationManualshould not supersede existing practices but should be considered as supplemental information Amana Fayetteville TN 37334 A higher standard of comfort He...

Page 2: ...il it today This will assist Amana in contacting you should any service or warranty information change in the future When filling in the registration card be sure to include the Model Manufacturing an...

Page 3: ...to be set on a floor that may become wet or damp at times the furnace should be supported above the floor on a concrete base sized approximately 1 1 2 larger than the base of the furnace ADDITIONAL L...

Page 4: ...al injury or property damage may occur if the furnace and other fuel burning appliances are not provided withenoughfreshairforpropercombustion and ventilation of flue gases Most homes require outside...

Page 5: ...th doors are considered a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be provided with two permanent openings co...

Page 6: ...vers and grilles will have 60 75 percent free area Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment oper...

Page 7: ...evious con ditions of use g If improper venting is observed during any of the above tests the common venting system must be corrected in accordance with the latest edition of the National Fuel Gas Cod...

Page 8: ...n can occur inside masonry chimneys when a single fan assisted Category I appliance 80 AFUE furnace is vented without adequate dilution air Do not connect an 80 furnace to a masonry chimney unless the...

Page 9: ...nd or Reline Fix 4 Cleanout free of debris Check 4 Reline Fix 4 Liner in good condition Check 5 Dilution air available Check 6 Complete the installation Check 7 Reline Fix 4 Reline Fix 4 No Yes Yes Ye...

Page 10: ...f the tile liner Rusted pieces of the metallic liner reline the chimney Fix 4 CHECK 5 LINER CONDITION If a metal liner is present it must be checked It cannot be assumed that all existing metal liners...

Page 11: ...relined Fix 4 FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The liner and cap roof assembly must then terminate above the...

Page 12: ...s very tall The vent connectors used are very long or have a large number of elbows Local experience indicates that flexible liners installed without insulation are likely to have condensation problem...

Page 13: ...irigid metallic tubing and metallic fittings Alumi num alloy tubing must not be used in exterior loca tions Listed gas appliance connectors used in accor dance with the terms of their listing must be...

Page 14: ...ugh the left side of the furnace the installer must supply a straight pipe to reach the exterior of the furnace Figure 17 Figure 17 Gas Inlet Through Left Side Counterflow A ground joint union drip le...

Page 15: ...ch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted s...

Page 16: ...ARNING To prevent death or personal injury due to electric shock disconnect electrical power before changing any electrical wiring CAUTION When servicing controls label all wires before disconnecting...

Page 17: ...ow voltage wiring may enter through the right or left side of the furnace as viewed for an upflow installation top or bottom for a horizontal installation See Specification Sheet for hole locations Ru...

Page 18: ...America Manual D A duct system must be installed in accordance with Stan dards of the National Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Syst...

Page 19: ...For air delivery of 1800 CFM or higher use two side returns or one side return plus bottom return Guide dimples locate the side and bottom return cutout locations Use a straight edge to scribe lines...

Page 20: ...er Continuous Light 1 Internal Control Failure 1 Flash 2 System Lockout 2 Flashes 3 Pressure Switch Stuck Closed 3 Flashes 4 Pressure Switch Stuck Open 4 Flashes 5 Open Limit Control 5 Flashes 6 Open...

Page 21: ...anation of the pos sible problem On new installations or if a functional part such as the gas valve pressure switch or limit control has been replaced verify that the furnace is operating properly aft...

Page 22: ...our screws This is intentional and not a manufacturing defect 3 As shipped the rollout protection device is located near the flame sensor end of the manifold assembly Re move and save the mounting scr...

Page 23: ...ontrol determines that a measurable combustion can not be established or maintained after three consecu tive tries four if flame is established then lost to turn on the furnace If a flame is not sense...

Page 24: ...ff the electrical power supply to the furnace 3 Set room thermostat to lowest possible setting 4 Remove the door on the front of the furnace Note This furnace is equipped with an ignition device to au...

Page 25: ...r consult with local utility Figure 41 Measuring Inlet Gas Pressure Alternate Method CHECK MANIFOLD PRESSURE A tapped opening is provided in the gas valve to facilitate measurement of the manifold pre...

Page 26: ...rnace as marked on the rating plate CHANGING BLOWER SPEEDS WARNING To avoid death or personal injury due to electricalshock turnoffpowertothefurnace before changing speed taps All furnaces ship at hig...

Page 27: ...er location and procedures for removal cleaning and replacing them If help is needed contact the installer of the furnace or a qualified servicer AIR FILTER UPFLOW FURNACES If the filter is in the fur...

Page 28: ...s are permanently lubricated No further lubrication is required INDUCED DRAFT BLOWER MOTOR The induced draft blower motor is permanently lubricated No further lubrication is required FLAME SENSOR INTE...

Page 29: ...the burners 5 Use bottle brush to clean burner insert and inside of burner 6 Replace burners and burner retention bracket inspect the burner assembly for proper seating of burners in retention slots 7...

Reviews: