4.2
Alarm relay 1 high setpoint
Display:
A1Hi
Range:
Any display value or
OFF
Default Value:
OFF
Displays and sets the high setpoint value for alarm relay 1. Use this high setpoint function if a relay
operation is required when the display value becomes equal to or more than the low setpoint value. To set
a high alarm value go to the
A1Hi
function and use the
^
or
v
push buttons to set the value required
then press
F
to accept this value. The high alarm setpoint may be disabled by pressing the
^
and
v
push buttons simultaneously. When the alarm is disabled the display will indicate
OFF
. If the relay is
allocated both a low and high setpoint then the relay will activate when the value displayed moves outside
the band set by the low and high setpoints. The value at which the relay will reset is controlled by the
A1HY
function.
Example
:
If
A1Hi
is set to
100
then relay 1 will activate when the display value is
100
or higher.
4.3
Alarm relay 2 low setpoint
Display:
A2Lo
Range:
Any display value or
OFF
Default Value:
OFF
Displays and sets the low setpoint value for alarm relay 2 which operates in the same manner as the
A1Lo
function. See
A1Lo
function for further description.
4.4
Alarm relay 2 high setpoint
Display:
A2Hi
Range:
Any display value or
OFF
Default Value:
OFF
Displays and sets the high setpoint value for alarm relay 2 which operates in the same manner as the
A1Hi
function. See
A1Hi
function for further description.
LDRSMANADD-2.3-0
17 of