Ama Tech AH-5 Installation Manual Download Page 21

 

20 

 

EEP 

ROM abnormality

 

 

2.

 

ROM trouble

 

When this abnormal warning often 
happens, please sent it to 
manufacture for inspecting and 
repairing

 

PID 

PID abnormality 

 

1.  Capacity of variable 

frequency drive and motor 
is not enough 

2.  Setting of target value or 

feedback value of PlD is 
unreasonable 

3.  P

eripheral equipment 

trouble 

1. 

Replace with variable 

frequency drive and motor 
with big capacity 

2. 

Check feedback gains setting, 
reset target value according to 
feedback 

3. 

Check whether peripheral 
feedback devices (such as 
sensor, potentiometer) and 
circuit are normal 

CPU 

CPU abnormality 

 

Peripheral electromagnetic 
interference is serious 

Reduce peripheral interference 

OLS 

Stall-proof 

Protection 

 

Motor is overloaded 

1. 

Reduce motor load 

2. 

Increase value of 06-01(P.22) 

NTC 

Module is 

overheated 

 

IGBT  module  temperature  of 
inversion side is over-high 

1. 

Reduce ambient temperature 

and improve ventilation 
condition 

2. 

Confirm whether fan of variable 

frequency drive normally 
operates 

OL2 

Over-torque 

abnormality 

 

1.  Motor is overloaded 
2.  Setting of parameters 

06-0S(P.155),06-09(P.156) 
is unreasonable 

1. 

Reduce motor load 

2.  Properly adjust set value of 

06-08(P.155),06-09(P.156) 

CPR 

CPU abnormality 

 

CPU program abnormality 

1. 

Check wiring 

Check parameter setting 

3. 

Reduce peripheral interference 

AErr 

3-5 terminal 

abnormality 

 

Disconnection of analog timing 
of 3-5 terminal is abnormal 

Please  see  02-24(P.184)  parameter 
instruction   

(6) Arranging the site environment: Clean Environment

 

Remove stuff from the site, place equipment in order, correctly check tools and clean 

Service Conditions of Equipment 

Environment 

Conditions 

Installation Site 

Interior 

Ambient 
Temperature 

-15~+55℃ 
For increasing product reliability, please use this product at the 
placewhere temperature cannot rapidly change. 

Humidity 

Below 95%RH 

Environment 

The place without corrosive gas and flammable gas 

Altitude 

Below 1000m 

Summary of Contents for AH-5

Page 1: ......

Page 2: ...1 Installation Guide Type Model to be installed Helicopter Fan AH 5 Helicopter Fan AH 6 Helicopter Fan AH 7...

Page 3: ...ation Structure Square Steel Beam Optional 11 1 Installation Structure Cement Beam Optional 12 1 Installation Structure Round Steel Beam Optional 13 2 Installing Main Machine Extension Fan Unit 14 3 I...

Page 4: ...to damaged or dangerous power supply Please do not try to solve circuit problem or trouble by yourself If you have any problem about installation of this fan please contact AmaTech WARNING For reducin...

Page 5: ...nce of National Fire Protection Association NFPA Fan must be located in the center of four 4 adjacent fire sprinklers The vertical distance between fan and flow deflector of fire sprinkler should be n...

Page 6: ...ad Current A 0 5 3 8A 0 46 2 8A 0 43 2 0A 3 Phase Voltage V 220 220 220 Max Affected Area m2 1300 1000 700 Wind Volume at Max Speed m3 min 14900 12400 10900 Noise Level dB 40 40 40 Fan Blade 5 5 5 Wei...

Page 7: ...n Unit 1 2 Fan Blades Box Fan Blade 5 3 Other Components Box Mounting Clamp 2 Universal Mount 1 Extension 1 Guy Wire Plate 2 Lamp Holder Plate 1 Lamp Holder 1 Airfoil 5 Galvanized Hex Bolt M12 60 4 pi...

Page 8: ...7 Pre Installation Components Inspection 2 3 Other Components Box 1 Mounting Clamp 2 Universal Mount 1 Extension 1 Guy Wire Plate 2 Water proof Cap 1 Winglet 5...

Page 9: ...M12 60 4 pieces M12 100 2 pieces Hex Socket Head Bolt M12 M12 100 2 pieces Hex Socket Head Bolt M12 M12 110 2 pieces Hex Bolt Nylok M12 60 10 pieces Self tapping Screw M4 M4 20 10 pieces Nylon Hex Lo...

Page 10: ...ce Installation Standard and Metric Wrench Kit Phillips Screwdriver and Flathead Screwdriver Standard and Metric Screw and Ratchet Kit 10 14 AWG Wire Stripper Standard and Metric General Wrench Kit Me...

Page 11: ...position position the Universal Mount under the I Beam assemble one Mounting Clamp with one side of the I Beam and then pre tighten them The above step will be repeated on the other side After finish...

Page 12: ...osition the Universal Mount under the Square Steel Beam assemble the Mounting Clamp with low edge of the Square Steel Beam and then pre tighten them and pre tighten all Hex Nuts on the Threaded Rods A...

Page 13: ...e L Type Bracket on the Cement Beam with the Expansion Bolts the above step will be repeated on the other side of Cement Beam bottoms of 2 L Type Bracket should be leveling Position the Universal Moun...

Page 14: ...allation position attach the Universal Mount under Round Steel Beam put U Type Fixing Rings on the Round Steel Beam and pre tighten them Pre tighten all nuts After finish apply loctite to all bolts th...

Page 15: ...Wire Plates on both sides then attach washers to outside of Guy Wire Plates insert Hex Socket Head Bolts tighten Hex Nuts to finish it torque to 60 NM Overhead operation 4 Stretch cable hose then thr...

Page 16: ...Tighten fan blades to airfoils with screws torque to 3 5 NM A Assemble them with fan unit by overhead operation B Avoid scratching surfaces of fan blades when installing fan blades apply loctite to a...

Page 17: ...s horizontal vertical and beautiful the distance between Cable Clamps is 1 5m Overhead and ground operation Attention Cables must be connected with same colors for example yellow green connect to yell...

Page 18: ...onnect cables to control system according to corresponding circuit colors 3 Use Multimeter to measure after finish turn on circuit breaker and power it on turn on fan for test counterclockwise rotatio...

Page 19: ...ame Grounding Terminal Notes There are no built in braking units in Frame A and no P and PR terminals Main Circuit Terminal Array of Various Machines Frame A Frame B Braking Resistor Connection Notes...

Page 20: ...current during deceleration OV0 Over voltage during stopping machine Voltage between terminal P and N is over high Check whether input power is normal OV1 Over voltage during acceleration 1 If there i...

Page 21: ...h 1 Reduce ambient temperature and improve ventilation condition 2 Confirm whether fan of variable frequency drive normally operates OL2 Over torque abnormality 1 Motor is overloaded 2 Setting of para...

Page 22: ...nt press power button 5 During fan running press power button again equipment will stop 6 When fan is running normally forbid to power off 7 After turn off fan and before the fan blades completely sto...

Page 23: ...1 2 Dead On Arrival DOA 1 2 1 Products shall be only confirmed as DOA when there are defects on arrival and trouble which is not caused by abnormal use of Products damage during freight or unauthorize...

Page 24: ...f equipment power when installing d This Product has been abused misused or incorrectly installed e Wrong wire connection f Products trouble caused by natural disasters or force majeure g Damage in fr...

Reviews: