Testing Ethernet Communication (Optional)
Required Items:
•
CAT5/6 Ethernet Cable
•
Laptop Computer Running Windows 7 or Windows 8
1. Locate the Ethernet port on the CPU board [Figure 27].
2. Connect the Ethernet cable to the Ethernet port.
3. Connect the other end of the Ethernet cable to the laptop
computer.
4. Launch
Command Prompt
on the computer by typing
CMD
in the '
Search programs and files
' field.
5. Enter the following command:
ping XXX.XXX.XXX.XXX,
where XXX.XXX.XXX.XXX is the IP address of the turnstile
[Figure 28].
6. A successful ping will result in the message shown in
[Figure 28]:
The following procedure is applicable to non-networked (standalone) turnstiles. For instructions on testing Ethernet
communication over a facility network, please refer to the
SU3500 User Guide
.
192.168.0.100 is the default IP address configured by Alvarado.
If the turnstile has been assigned a different network IP
address, ping that IP address instead. Contact your system
administrator for network information.
NOTE
NOTE
Fig. 28
Ping Results
Fig. 27
CPU Board
Ethernet
Port