Fan Location and Speed Information
Fan Location
The KVM Over the NET™ switch has 6 fans that feed realtime fan speed
information to the WinClient / Java Client Device Management page.
The speed of each of the fans in the above image are shown on the
web page. See page 147 for details.
Fan Speed
The fan speed automatically adjusts according to temperature as follows:
If any sensor senses that the temperature is greater than 32° C, all the fans
are set to spin at half speed.
If any sensor senses that the temperature is greater than 45° C, all the fans
are set to spin at full speed.
When all four sensors sense that the temperature is less than 40° C, all the
fans return to half speed.
When all four sensors sense that the temperature is less than 30° C, all the
fans turn off.