Altronix AL800ULADA Installation Manual Download Page 1

Rev. 122000

AL800ULADA

NAC Power Extender

Installation Guide

Summary of Contents for AL800ULADA

Page 1: ...Rev 122000 AL800ULADA NAC Power Extender Installation Guide ...

Page 2: ...Agency Listings UL Listed for Control Units and Accessories for Fire Alarm Systems UL 864 and UL Listed Standard for Safety for Fire Protective Signaling Systems UL 1481 MEA NYC Department of Buildings Approved CSFM California State Fire Marshal Approved FM Factory Mutual Approved NFPA 72 Compliant Input Power input 115VAC 60 Hz 3 2 amp Two 2 Class A or two 2 Class B FACP inputs Two 2 NC dry conta...

Page 3: ...5VAC 60Hz dedicated to the Fire Alarm System Fig 1 pg 3 Connect green lead to earth ground 3 Set switch SW1 on Power Supply Board for desired output voltage Open for 24VDC factory set Close for 12VDC 4 Measure output voltage before connecting devices This helps avoid potential damage 5 Connect battery to terminals marked BAT on the Power Supply Board battery leads included Use two 2 12VDC batterie...

Page 4: ...lsing input Strobe Sync 1 2 Enables Strobe synchronization mode 1 30 ms pulse every 9 second Mode 1 3 Will accept a steady or pulsing input Gentex Strobe Sync 1 2 3 Enables Strobe synchronization mode 2 40 ms pulse every 1 second Mode 2 Will accept a steady or pulsing input System Sensor Strobe Sync 2 1 3 Enables Strobe synchronization mode 3 50 ms pulse every 95 second Mode 3 Will accept a steady...

Page 5: ...plies may be connected to these terminals If this option is chosen the EOL resistor must be terminated at the last device C DRY1 N C An open across these terminal pairs will cause the selected outputs chosen to drive C DRY2 N C notification appliances The designated outputs are set by output switches OUT1 through Dry input OUT4 Output Programming Selection Table pg 4 Note these inputs are trigger ...

Page 6: ...C are closed and N C and C are open BAT BAT Stand by battery input leads provided Use two 2 12VDC batteries wired in series for 24VDC operation Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level Power Supply Output Specifications Chart Battery Te...

Page 7: ... limited Fig 2 Horn Legend Strobes Horn Strobes OPEN SWITCH CLOSED SWITCH Switch Detail SW1 DC SW2 OUT1 OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT AUX NO REMOTE C 1 2 3 4 O N 1 2 3 4 O N 1 2 3 4 O N 1 2 3 4 O N NO C NC C FAULT NC AUX RESET OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC IN1 IN1 IN2 IN2 C DRY1 NC RET1 RET1 RET2 RET2 C DRY2 NC OUT2 OUT3 OUT4 INPUT SELECT TEMPORAL STROBE S...

Page 8: ...between the board and standoff of the lower right power supply board mounting screw Fig 4C DC AC AC BAT OPEN 24V SW1 CLOSED 12V DC AC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC3 IC2 AC FAIL NC C NO BAT FAIL NC C NO These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP s IN1 and IN2 N O Reset Switch Digital Communicator or Local Annuncia...

Page 9: ...the Input to Output Follower Mode Dip Switch 1 ON and disable the Strobe Sync Mode Dip Switch 2 OFF Typical Sync Module Hookups Fig 5 Synchronization using one 1 synchronization module with four 4 outputs Fig 6 Synchronization using multiple synchronization modules Note When using this configuration you must disable the Input to Output Follower Mode Dip Switch 1 OFF and disable the Strobe Sync Mod...

Page 10: ...T1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC IN1 IN1 IN2 IN2 C DRY1 NC RET1 RET1 RET2 RET2 C DRY2 NC OUT2 OUT3 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC UPPER TERMINALS LOWER TERMINALS 2 2K EOL 2 2K EOL 2 2K EOL 2 2K EOL AL800LGK Horn Legend Strobes Horn Strobes When using combination horn strobes Follow manufacturer s instructions for powering horns and strobes indepen...

Page 11: ... 875 1 1 3 9 97 13 53 2 2 25 3 68 4 56 1 22 1 22 3 25 1 13 25 2 1 22 12 15 5 8 4 5 2 25 3 68 4 56 1 22 1 25 2 2 1 Enclosure Dimensions 15 5 H x 12 W x 4 5 D 11 ...

Page 12: ...Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIAL800ULADA G29E MEMBER Notes Altronix is not responsible for any typographical errors 12 ...