Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired locationMark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 11, 12).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided 
  green grounding conductor lead. Connect unswitched AC power (115VAC, 60Hz) to the terminals marked 
  [L, N] (Fig. 1, pg. 4). Green “AC” LED on power supply board will turn on. This light can be seen through 
  the LED lens on the door of the enclosure. Use 14 AWG or larger for all power connections (Battery, DC 
  output, AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
  Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input, 
  DC Output, Battery Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 
  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 
  service personnel.
  For Fire Alarm applications the outputs are “Special Applications” only see list (refer to Appendix A, pg. 8)
  For other devices contact Underwriters Laboratories to ensure compatibility.
3. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1b, pg. 4) to the appropriate position 
  (Power Supply Voltage Output Selections Chart, pg. 3).
4. Measure output voltage before connecting any devices to ensure proper operation. Improper or high voltage 
  will damage these devices. When servicing the unit, AC mains should be removed.
5. Connect device(s) to be powered:
  a.  For AL600ULX(R) Power Supply: connect devices to the terminals marked [+ DC –] (Fig. 1, pg. 4).
  b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked  
    [1P & 1N] through [4P & 4N] (Fig. 2a & 2b, pg. 7) or 1 to 8 marked [1P & 1N] through [8P & 8N]
  (Fig. 3a & 3b, pg. 7), carefully observing correct polarity.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 
  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
7. Connect appropriate signaling notification devices to the terminals marked [AC FAIL & BAT FAIL] 
  (Fig. 1, pg. 4) supervisory relay outputs.
 

Note: When used in fire alarm or access control applications, “AC Fail” relay should be utilized 

  to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper (Fig. 1a, pg. 4).
8.  Please ensure that the cover is secured with the provided Key Lock.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for the proper 
voltage level (Power Supply Voltage Output Specifications Chart, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage 
both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the 
battery connection wires.
Note: Maximum charging current under discharges is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

Summary of Contents for AL600ULX Series

Page 1: ...ed Outputs AL600ULPD8 Eight 8 Fuse Protected Outputs AL600ULXPD16 Sixteen 16 Fuse Protected Outputs AL600ULPD4CB Four 4 PTC Protected Outputs AL600ULPD8CB Eight 8 PTC Protected Outputs AL600ULXPD16CB...

Page 2: ...ut Agency Listings UL Listings and File Numbers AL600ULX AL600ULXR AL600ULXX 1 6 UL File S4707 UL 294 UL Listed for Access Control System Units UL 1481 UL Listed Power Supplies for Fire Protective Sig...

Page 3: ...nd electronically regulated outputs Short circuit and thermal overload protection Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery w...

Page 4: ...Module s INPUT Divider Earth Ground DC BAT FAIL NC C NO NC C NO BAT AC FAIL DC AC BAT L G N 5A 250V AC Delay Battery connection non power limited non power limited CAUTION Optional rechargeable stand...

Page 5: ...setting SW1 Fig 1b pg 4 to the appropriate position Power Supply Voltage Output Selections Chart pg 3 4 Measure output voltage before connecting any devices to ensure proper operation Improper or hig...

Page 6: ...eutral Do not use the G terminal DC 12VDC or 24VDC 6A continuous non power limited output AC Fail NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energiz...

Page 7: ...PUT R1 LED From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V Non Power Limited DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs PD8UL POWER D...

Page 8: ...35o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 3...

Page 9: ...AL600ULX Series 9 Notes...

Page 10: ...10 AL600ULX Series Notes...

Page 11: ...342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 2...

Page 12: ...31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23...

Reviews: