Overview:

Altronix AL300ULXD power supply/charger converts a 115VAC, 50/60Hz or 230VAC, 50/60Hz input into a 
power-limited 12VDC or 24VDC output (see specifications)

Specifications:

AL300ULXD

Power Supply/Charger

Agency Listings:

• 

UL 294*  Safety Access Control System Units,  

 

UL 603  Power Supplies for Use with

   

Burglar-Alarm Systems, 

 

UL 1069  Hospital Signaling and 

   

Nurse Call Equipment,

 

UL 1481  Power Supplies for Fire-Protective 

   

Signaling Systems.

• 

CE 

European Conformity.

Input:

•  115VAC, 50/60Hz, 0.9A or 
  230VAC, 50/60Hz 0.45A.

Output:

•  12VDC or 24VDC selectable output.
•   12VDC or 24VDC @ 2.5A supply current.
•  Class 2 Rated power-limited output.
•  Filtered and electronically regulated output.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Automatic switch over to stand-by battery 
  when AC fails.
•  Maximum charge current 0.6A.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Low battery supervision (form “C” contacts). 

Visual Indicators:

•  AC input and DC output LED indicators.

Features:

•  Low battery disconnect.
•   Unit is complete with transformer, power supply, 
  grey enclosure, and cam lock.
•  Battery leads included.

Enclosure Dimensions 

(H x W x D approx.)

:

  15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
  Accommodates up to two 12VDC/12AH batteries.
  For a red enclosure add an “R” suffix to the 
  part #, e.g. AL300ULXDR.

*Access Control Performance Levels: 
Destructive Attack - I; Endurance - IV; Line Security - I; Stand-by Power - IV.

Power Supply Output Selection:

Output

Switch Position

12VDC

SW1, 2 - ON, SW3, 4 - OFF

24VDC

SW1, 2 - OFF, SW3, 4 - ON

Stand-by Specifications:

Output

4 hr. of Stand-by and

5 Minutes of Alarm

24 hr. of Stand-by and

5 Minutes of Alarm

60 hr. of Stand-by and

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 2.5A

Alarm = 2.5A

Stand-by = 1.0A

Alarm = 2.5A

Stand-by = 300mA

Alarm = 2.5A

24VDC / 12AH Battery

Stand-by = 200mA

Alarm = 2.5A

24VDC / 40AH Battery

Stand-by = 2.5A

Alarm = 2.5A

Stand-by = 1.0A

Alarm = 2.5A

Stand-by = 300mA

Alarm = 2.5A

Summary of Contents for AL300ULXD

Page 1: ...t 0 6A Supervision AC fail supervision form C contacts Low battery supervision form C contacts Visual Indicators AC input and DC output LED indicators Features Low battery disconnect Unit is complete with transformer power supply grey enclosure and cam lock Battery leads included Enclosure Dimensions H x W x D approx 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm Accommodates up to two 12VDC 12AH bat...

Page 2: ...en batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect battery to terminals marked BAT Fig 1 pg 3 Use two 2 12VDC batteries connected in series for 24VDC operation battery leads included 6 Connect appropriate signaling notification devices to AC Fail and Low battery supervisory relay ...

Page 3: ... 2 1 ON AC AC BAT AC DC Class 2 power limited non power limited Input 115VAC 50 60Hz 0 9A or 230VAC 50 60Hz 0 45A Fig 1 5 4 3 2 1 BLACK YELLOW BLUE WHITE LINE NEUTRAL 115VAC Input 230VAC Input Fig 2 115VAC Input Fig 3 230VAC Input 5 4 3 2 1 BLACK YELLOW BLUE WHITE ...

Page 4: ...5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimens...