background image

Overview:

AL125ULB is a power-limited power supply/charger that converts a low voltage AC input into two individually 
PTC protected 12VDC or 24VDC outputs (see specifications). They are intended for use in applications requiring 
UL Listing for Access Control (UL 294) and applications requiring an interface with Fire Alarm Control Panels.

Specifications:

*Note: 

When unit is powered by battery back up (AC Fail condition), the voltage range is 9.3V-13.2V and 

 

19.55V-26.4V for 12 and 24 volt operation respectively. 

Power Supply Output Specifications:

Output VDC

Switch Position Max. Stand-by Load DC Max. Alarm Load DC Battery (optional)

12VDC

SW2 OFF

1A

1A

12VDC

24VDC

SW2 ON

1A

1A

24VDC

Stand-by Specifications:

Output

4 hr. of Stand-by and 

5 min. of Alarm

Output

4 hr. of Stand-by and 

5 min. of Alarm

12VDC/4AH Battery

Stand-by = 0.5A

Alarm = 1A

12VDC/7AH Battery

Stand-by = 1A

Alarm = 1A

24VDC/4AH Battery

Stand-by = 0.5A

Alarm = 1A

24VDC/7AH Battery

Stand-by = 1A

Alarm = 1A

Installation Instructions:

The units should be installed in accordance with article 760 of The National Electrical Code and NFPA 72 as 
well as all applicable Local Codes.
See Terminal Identification Chart on page 2 for a description of each terminal function.
1. Mount unit in the desired location/enclosure.
2. Connect 24VAC from a UL Listed 40VA plug-in transformer to the terminals marked [XFMR].
 

Keep power-limited wiring separate from non power-limited wiring 

  (115VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
3.  Measure output voltage before connecting any devices to ensure proper operation.
  Improper or high voltage will damage these devices.
4.  Set the desired DC output voltage by setting switch SW2 (Fig. 1a - Application Diagram, pg. 2) to the 
  appropriate position (Power Supply Output Specifications Table, pg. 1).
5. Connect Fail-Safe locking devices to the terminals marked [COM--   and LOCK+]. Connect Fail-Secure \ 
  locking  devices to the terminals marked [COM--   and ] (Fig. 1 - Application Diagram, pg. 2). 
6. Connect normally open access control device (i.e. cardreader, request to exit device, access control system) 
  to the terminals marked TRG INPUT [NO, GND] (Fig. 1 - Application Diagram, pg. 2). 
7. Connect FACP interface to the terminals marked [FACP1 and FACP2]. Wire the 2.2K resistor (supplied) 
  in series for a normally closed input or in parallel for a normally open input (Fig. 1 - Application Diagram, 
  pg. 2). 
If required, set the latching FACP interface mode by closing SW1 (Fig. 1a - Application Diagram, 
  pg. 2)
, and connect a normally open reset device to the terminals marked RESET [NO, GND].
8. Connect battery to the terminals marked [+ BAT -- ] (battery leads included). Use two (2) 12VDC batteries 
  connected in series for 24VDC operation.

AL125ULB 

Access Control Power Supply/Charger

Agency Listings:

•  UL Recognized component.
•  NFPA 101 (Life Safety).

Input Rating:

• 24VAC/40VA.

Output Rating:

•  12VDC or 24VDC selectable, 
  Class 2 Rated power-limited outputs.
•  1A total supply current @ 12VDC or 24VDC.
•  Filtered and electronically regulated output.

*

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Maximum charge current: 400mA.
•  Automatic switch over to stand-by battery when 
  AC fails.

Special Features:

•  “NO” trigger input.
•  Supervised Fire Alarm Disconnect
  (Latching with reset or Non-Latching).

Board Dimensions 

(L x W x H)

:

  3.8” x 3.0” x 1.5” (96.5mm x 76.2mm x 38.1mm).

Reviews: