P011787 – Rev. R
106 VDC
for the P1502W, P1502WLP & P1502WHP models
9.8.4
Close Front Panel.
If the voltage does not measure as indicated above, this is an indication that the
Cycle Timer is defective and should be replaced. See sections 11.3 for part detail
and 11.5 for ordering information.
9.9 Testing Air Dryer Fan
NOTE:
To test the fan, the cabinet temperature must be above 90
F.
9.9.1
Place your hand outside the
dryer to feel for air being
blown outwards.
NOTE:
The fan will turn OFF
when the cabinet temperature is
below 80
F.
If the fan is not blowing air outwards as described:
Verify the cabinet temperature is above 90
F.
Check for loose wiring. Refer to the Wiring Diagram (section 14.1 )
Replace defective fan (see sections 11.1 for part detail and 11.5 for
ordering information).
Replace defective Control Board if fan does not respond properly to
temperature changes (see sections 11.2 for part detail and 11.5 for
ordering information).
9.10 Testing Safety Relief Valve
9.10.1
Open Front Panel (section 8.6 ).