Application Notes
P54x/EN AP/La4
MiCOM P543, P544, P545 & P546
(AP) 6-11
AP
Relay sensitivity when |
bias| > Is2:
For |
bias| >
s2, the relay would operate if
|
diff| > k2 |
bias| - (k2 - k1)
s2 +
s1
or |
F| > k2 (|
L| + 0.5 |
F|) - (k2 - k1)
s2 +
s1
or
(1 - 0.5 k2) |
F| > (k2 |
L| - (k2 - k1)
s2 +
s1)
or |
F| > (k2 |
L| - (k2 - k1)
s2 +
s1) / (1 - 0.5 k2)
For
s1 = 0.2 pu, k1 = 30%,
s2 = 2.0 pu and k2 = 100%, then,
1. for
|
L| = 2.0 pu, the relay would operate if |
F| > 1.6 pu
2. for
|
L| = 2.5 pu, the relay would operate if |
F| > 2.6 pu
Fault resistance coverage:
Assuming the fault resistance, RF, is much higher than the line impedance and source
impedance, then for a 33 kV system and 400/1 CT:-
|
F|
= (Vph-n /RF) * (1/CT ratio) pu
=
(33000
/ 3 )/RF)/400 pu
=
47.63/RF
pu
Based on the above analysis, the relay will detect a fault current in excess of 0.59 pu with a
load current of 1 pu flowing. The fault resistance would have to be less than 47.63/0.59 =
81
in this case.
With a short time overload current of 2.0 pu, the relay will be able to detect a fault resistance
of 47.63/1.6 = 30
or lower.
2.1.3
CT ratio correction (all models)
Ideally, the compensated current values should be arranged to be as close as possible to
relay rated current to provide optimum relay sensitivity.
If there is not mismatch between the CTs, the CT correction factor should be set to 1:1.
2.1.4
Transformers in zone applications (P543 & P545 models)
In applying the well established principles of differential protection to transformers, a variety
of considerations have to be taken into account. These include compensation for any phase
shift across the transformer, possible unbalance of signals from current transformers either
side of windings, and the effects of the variety of earthing and winding arrangements. In
addition to these factors, which can be compensated for by correct application of the relay,
the effects of normal system conditions on relay operation must also be considered. The
differential element must restrain for system conditions which could result in maloperation of
the relay, such as high levels of magnetizing current during inrush conditions.
In traditional transformer feeder differential schemes, the requirements for phase and ratio
correction were met by correct selection of line current transformers. In the P543 and P545,
software interposing CTs (ICTs) are provided which can give the required compensation.
The advantage of having replica interposing CTs is that it gives the P54x relays the flexibility
to cater for line CTs connected in either star or delta, as well as being able to compensate
for a variety of system earthing arrangements. The P543 and P545 relays also include a
magnetizing inrush restraint facility.
Note:
The P544 and P546 relays do not include any of the above features,
except CT ratio mismatch compensation, and as such would not be
suitable for the protection of in-zone transformer feeders.
On P543 or P545 relays where capacitive charging current compensation is available, there
is a setting to select if capacitive charging current compensation is used or if interposing CTs
are used.
Summary of Contents for MiCOM P54 Series
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Page 6: ...P54x EN SS H11 Safety Section SS...
Page 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Page 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Page 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Page 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Page 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Page 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Page 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Page 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Page 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Page 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Page 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Page 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Page 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Page 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Page 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Page 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Page 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Page 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Page 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Page 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Page 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Page 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Page 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Page 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Page 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Page 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Page 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Page 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Page 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Page 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Page 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Page 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Page 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Page 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Page 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Page 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Page 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Page 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Page 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Page 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Page 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Page 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Page 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Page 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Page 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Page 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Page 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Page 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Page 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Page 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Page 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Page 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Page 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Page 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Page 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Page 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Page 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Page 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Page 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Page 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Page 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Page 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Page 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Page 1023: ......