Operation
P54x/EN OP/La4
MiCOM P543, P544, P545 & P546
(OP) 5-81
OP
AR Timer Block
(3rd & 4th stages only)
1
Phase Overcurrent Timer Block
(Independent for each stage)
Fast VTS
Block
Directional
Check
&
1
1
Directional
Check
&
Directional
Check
&
IDMT/DT
&
C Phase Start
C Phase Trip
IDMT/DT
&
IDMT/DT
&
B Phase Start
B Phase Trip
A Phase Start
A Phase Trip
VAB Polarizing
Memory
VAB Polarizing
Voltage
C Phase
Overcurrent
VCA Polarizing
Memory
VCA Polarizing
Voltage
B Phase
Overcurrent
VBC Polarizing
Memory
VBC Polarizing
Voltage
A Phase
Overcurrent
P1628ENb
Figure 54 Directional overcurrent logic
Any of the four overcurrent stages may be configured to be directional noting that IDMT
characteristics are only selectable on the first two stages. When the element is selected as
directional, a VTS Block option is available. When the relevant bit is set to 1, operation of
the Voltage Transformer Supervision (VTS), will block the stage if directionalized. When set
to 0, the stage will revert to non-directional upon operation of the VTS.
1.26
Synchronous polarization
For a close up three-phase fault, all three voltages will collapse to zero and no healthy phase
voltages will be present. For this reason, the MiCOM P54x relays include a synchronous
polarization feature that stores the pre-fault voltage information and continues to apply it to
the directional overcurrent elements for a time period of 3.2 seconds. This ensures that
either instantaneous or time delayed directional overcurrent elements will be allowed to
operate, even with a three-phase voltage collapse.
1.27
Thermal overload protection
The relay incorporates a current based thermal replica, using rms load current to model
heating and cooling of the protected plant. The element can be set with both alarm and trip
stages.
The heat generated within an item of plant, such as a cable or a transformer, is the resistive
loss (
2R x t). Therefore, heating is directly proportional to current squared. The thermal
time characteristic used in the relay is therefore based on current squared, integrated over
time. The relay automatically uses the largest phase current for input to the thermal model.
Equipment is designed to operate continuously at a temperature corresponding to its full load
rating, where heat generated is balanced with heat dissipated by radiation etc.
Over-temperature conditions therefore occur when currents in excess of rating are allowed to
flow for a period of time. It can be shown that temperatures during heating follow
exponential time constants and a similar exponential decrease of temperature occurs during
cooling.
The relay provides two characteristics that may be selected according to the application.
Thermal overload protection may be disabled by DDB 478
Inhibit Thermal >
.
Summary of Contents for MiCOM P54 Series
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Page 6: ...P54x EN SS H11 Safety Section SS...
Page 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Page 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Page 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Page 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Page 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Page 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Page 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Page 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Page 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Page 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Page 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Page 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Page 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Page 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Page 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Page 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Page 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Page 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Page 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Page 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Page 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Page 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Page 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Page 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Page 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Page 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Page 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Page 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Page 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Page 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Page 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Page 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Page 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Page 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Page 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Page 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Page 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Page 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Page 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Page 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Page 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Page 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Page 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Page 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Page 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Page 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Page 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Page 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Page 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Page 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Page 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Page 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Page 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Page 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Page 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Page 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Page 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Page 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Page 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Page 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Page 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Page 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Page 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Page 1023: ......