GEM80-500 Series Controller
3. Configuration of Optional Modules
(08/04)
GEM80-500 Technical Manual (T2025En)
Page 3-13
Table
3-4 P-Tables
for Printer/Keyboard Port
Port 1
Port 2
Port 3
Port 4
Contents
P10
P30
P110
P130
Baud rate (110 to 19,200)
P11 P31 P111 P131 0
P12
P32
P112
P132
0 = Printer Mode
1 = Terminal Mode
2 = Free Format Mode
P13
P33
P113
P133
Number of characters per line (1 to 132)
P14
P34
P114
P134
Number of padding characters (1 to 131)
P15 P35 P115 P135 Parity
Enable
0 = 8 data bits no parity bit
1 = 7 data bits plus 1 parity bit
2 = 8 data bits plus 1 parity bit
P16 P36 P116 P136 Parity
Select
0 = Even parity
1 = Odd parity
P17 P37 P117 P137 Not
used
Operation of a Printer/Keyboard Port
The Printer/Keyboard Port can operate in either 'Direct Mode', 'Terminal Mode' or in
'Free Format Mode'.
Note:
This port will operate in all controller operating states, i.e. halted, running, normal
input and test inputs.
Full details of each mode of operation are included in the GEM80-400 T1614
Technical Manual.
3.8.4 Installation
Installation of the 9714-4020 Serial Communications Module is described at Section 6.
3.9
TCP/IP Ethernet Module 9716-4020
The Ethernet Module uses standard PC104+ hardware and offers up to 50 virtual
simultaneous connections. It has a programming connection available for use with a
suitable GEM80 Programming Package.
Refer to the T2011 GEMLAN-T Technical Manual for full details about use with the
GEM80-500 Controller.
3.9.1 Ethernet
Connection
Connection to the 9716-4020 Ethernet Module is by the standard Ethernet Connector
mounted on the front panel of the controller. The Ethernet interconnecting cable for
the controller should be less than 2 m in length and meet the EMC Requirements
outlined in the T2011 GEMLAN-T Technical Manual.
For installation of the 9716-4020 TCP/IP Ethernet Module see Section 6.