Installation Location and Matters Needing Attention

2

Installation Location and Matters Needing Attention

The installation of the unit must comply with the national and local safety regulations. The 

installation quality directly affects the normal use, so the user should not carry out the installation 
personally. Instead, the installation and debugging should be done by the professional personnel. 
Only after that, can the unit be energized.

1  How to select the installation location for the indoor unit

a.  Where there is no direct sunlight.
b.  Where the top hanger, ceiling and the building structure are strong enough to withstand the weight of 

the unit.

c.  Where the drain pipe can be easily connected to outside.
d.  Where the flow of the air inlet and outlet are not blocked.
e.  Where the refrigerant pipe of the indoor unit can be easily led to outside.
f.  Where there is no inflammable, explosive substances or their leakage.
g.  Where there is no corrosive gas, heavy dust, salt mist, smog or moisture.

 CUATION

The unit which is installed in the following places is likely to run abnormally. If unavoidable, please 

contact the professional personnel at the 

ALPICAIR

 appointed service center

  Where is full of oil; 

② 

Alkaline soil off the sea;

③ 

Where there is sulfur gas(like sulfur hot spring); 

Where there are devices with high frequency (like wireless devices, electric welding devices, or 

medical equipments); 

⑤ 

Special circumstances.

2  Electric Wiring

a.  The installation must be done in accordance with the national wiring regulations.
b.  Only the power cord with the rated voltage and exclusive circuit for the air conditioning can be used.
c.  Do not pull the power cord by force.
d.  The electric installation should be carried out by the professional personnel as instructed by the local 

laws, regulations and also this manual.

e.  The diameter of the power cord should be large enough and once it is damaged it must be replaced by 

the dedicated one.

f.  The earthing should be reliable and the earth wire should be connected to the dedicated device of the 

building by the professional personnel. Besides, the air switch coupled with the leakage current protection 
switch must be equipped, which is of enough capacity and of both magnetic and thermal tripping functions in 
case of the short circuit and overload.

3  Earthing Requirements

a.  The air conditioner is classified into the Class I appliances, so its earthing must be reliable.
b.  The yellow-green line of the air conditioner is the earth line and can not be used for other purpose, cut 

off or fixed by the self-tapping screw; otherwise it would cause the hazard of electric shock.

c.  The reliable earth terminal should be provided and the earth wire can not be connected to any of the 

following places

Summary of Contents for ATMI-26HPDC1

Page 1: ...atch Series R410A GMV Multi VRF System Indoor Unit For European Union Applicable models ATMI 26HPDC1 ATMI 36HPDC1 ATMI 53HPDC1 ATMI 61HPDC1 ATMI 65HPDC1 Please read this manual carefully before the in...

Page 2: ......

Page 3: ...this case they can back to the normal condition by harmonizing their running modes the cooling mode is compatible with the dehumidifying mode and the fan mode can go with any other mode If the supply...

Page 4: ...Check of the Indoor Unit 6 5 Installation of the Air Supply Duct 6 6 Drawings of the Air Supply Outlet and Return Air Inlet 7 7 Installation of the Return Air Duct 8 8 Installation of the Condensate...

Page 5: ...object into the air outlet inlet grille Please take notice of the supporting frame of the unit to see if it is damaged over the long time period of use Never refit the unit and contact the sales agen...

Page 6: ...ur hot spring Where there are devices with high frequency like wireless devices electric welding devices or medical equipments Special circumstances 2 Electric Wiring a The installation must be done i...

Page 7: ...Attention 3 Running water pipe Coal gas pipe Sewage pipe Other places where the professional personnel think unreliable 4 Accessories for Installation Refer to the packing list for the accessories of...

Page 8: ...I 36HPDC1 ATMI 53HPDC1 ATMI 61HPDC1 ATMI 65HPDC1 Fig 1 Table 1 Outline Dimensions Item Model A B C D E F G H I J ATMI 26HPDC1 742 491 662 620 700 615 782 156 200 635 ATMI 36HPDC1 ATMI 53HPDC1 942 491...

Page 9: ...away from the TV set or radio to avoid the image interference and noise even if 1m is kept the noise may be produced due to the strong electric wave b Installation of the Indoor Unit 1 Insert the M10...

Page 10: ...thickness of the sponge depends on the actual installation environment 4 Horizontality Check of the Indoor Unit After the installation of the indoor unit its horizontality must be checked to make sur...

Page 11: ...rn air duct For the unit with the auxiliary electric heating function if the round duct is to be adopted then the straight length of the transition duct can not be less than 200mm The duct is either r...

Page 12: ...duct to the return air outlet of the unit by rivets and the other to the return air louver For the sake of the convenience to freely adjust the height a cutting of canvas duct will be helpful which ca...

Page 13: ...connection of the drain pipe and device do not impose too much force on the pipe on one side of the device and the pipe should be fixed as close as to the device c The drain pipe can be the ordinary h...

Page 14: ...e The installation height of the lift pipe should be less than 850mm It is recommended to set an inclination angle 1 2 for the lift pipe toward the drainage direction If the lift pipe and the unit for...

Page 15: ...the joint to see if it leaks or not If this unit is installed in the newly built house it is suggested to take this test prior to the ceiling decoration 13 Piping a Let the flare end of the copper pi...

Page 16: ...to prevent the condensate water overflowing 2 Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall During the wrapping the later circle should cover half o...

Page 17: ...ccordance with the wiring diagram otherwise the improper wiring would cause the air conditioning unit running abnormally or damaged Do not let the electric wires touch the refrigerant pipe the compres...

Page 18: ...POWER INDOOR UNIT A INDOOR UNIT B INDOOR UNIT C INDOOR UNIT D XT5X T4 XT3X T2 XT1 OUTDOOR UNIT N L Fig 21 GWHD 42 NK3AO POWER INDOOR UNIT A INDOOR UNIT B INDOOR UNIT C INDOOR UNIT D OUTDOOR UNIT INDOO...

Page 19: ...g Current A Input Power W Recommended Power Cord Sectional Area Pieces Type Model Indoor Fan Motor Cooling Heating Cooling and Heating 220 240V 50Hz 0 406 75 575 1 0 4 220 240V 50Hz 0 348 65 865 1 0 4...

Page 20: ...8 Working Temperature Range Indoor side state Outdoor side stae Dry bulb temp Wet bulb temp Dry bulb temp Wet bulb temp Rated Cooling 27 19 35 24 Max cooling 32 23 48 26 Min cooling 21 15 18 Rated Hea...

Page 21: ...temperature is too high poor heating effect The air filter screen is too dirty or clogged The door or window is not closed fully The set temperature is too low uncontrollable controller If the remote...

Page 22: ...onditioning unit is used under the environment with heavy dust the air filter should be cleaned often generally once every two weeks b Maintenance before seasonal use 1 Check if the air inlet outlet o...

Page 23: ......

Page 24: ...66129909217...

Reviews: