DLM-600 installer & user manual Rev. 1.3
16-11-2011
10 / 39
RETURN TO FACTORY DEFAULT
To set the DLM-600 back to the factory defaults the DLM-600 must first be powered down. Then press
and hold the S4 button and connect the power again. Hold the S4 button until the OP2 led illuminates.
JUMPERS AND LED’S
figure 1.
figure 2.
Jumpers and LED’s
figure 3. LED table and Jumper table
LED
Colour
Function when LED illuminates
Jumper Function
Normal position
OP2 green
Run
J11
Override.tamper
Open
OP3
red
Dialer is transmitting an alarm
J71
PSTN loop
monitoring
Pin 1 (top) en 2
–
open
Pin 2 and 3 (bottom)
–
short circuited
OP4
orange
Message in buffer / GPRS dialer ready J39
Reset
Open
OP5
green
Watchdog is active
J40
Watchdog
Open
OP8
red
GSM module:
Fast flashing:
GSM module is starting
up
Slow flashing:
GSM/GPRS module is
ready
On continuous:
GSM (Voice) is active
FWE
J44
MD
J43
Programming:
Pin 1 (left) and 2
–
enable
Pin 2 and 3 (right)
–
protect
Pin 1(left) and 2
–
run
Pin 2 and 3 (right) - flash
OP9
red
PSTN Line and CMK connected
J41+ J42 RS485 pull-up/down Do not use
LED’s OP3,
OP4, OP2:
zie LED
tabel
(figure 3)
Jumper J11 for
override
tamper
switch
Jumper J32
voor keuze
n.o. of n.c. van
relais 1 en 2
Jumpers J39, J40,
J43 and J44; see
table
Jumper J71
for
PSTN loop
monitoring
LED OP8:
see LED
table
(figure 3)
LED OP5:
see LED
table
(figure 3)
LED OP9:
see LED table
(figure 3)